background image

18-GE15D1-2

9

Installer’s Guide

Rail

Figure 16. Mounting Installation Options

for Horizontal Applications

HORIZONTAL RIGHT

1.

Unit is shipped from the factory in the horizontal
right configuration. Unit conversion is not re-
quired.

2.

If the unit is suspended, it must be supported
from the bottom near both ends as well as the
middle to prevent sagging. The service access
must remain unobstructed. If the unit is sup-
ported along the length of the front and back
with rails, the air handler only needs to be sus-
pended at both ends. See Figure 16.

3.

If the unit is not suspended it must be supported
as mentioned above and isolated carefully to pre-
vent sound transmission. Vibration isolators (field
supplied) must be placed under the unit.

4.

It is always recommended that an auxiliary drain
pan be installed under a horizontal Air Handler
(See Condensate Drain Piping) to prevent pos-
sible damage to ceilings.

5.

Isolate the auxiliary drain pan from the unit or
from the structure.

6.

Connect the auxiliary drain line to a separate
drain line (no trap is needed in this line) and ter-
minate according to local codes.

7.

If a return duct is connected to the air handler, it
must be the same dimensions as the return
opening shown in Figure 17 and the outline
drawing on page 21.

8.

Openings where field wiring enters the
cabinet must be completely sealed.

 Location

of power entry is shown on the outline drawing.
Use 2.5" clear stickers to seal all unused electri-
cal knockouts. See Figure 13.

9.

After ductwork connections are made, seal air-
tight and per local codes.

Содержание 4TEE3D01B1000A

Страница 1: ...from the factory in the upflow or horizontal right configuration Variable Speed Communicating Air Handlers with Integrated Whole House Air Cleaner 4TEE3D01B1000A 4TEE3D02B1000A 4TEE3D03B1000A NOTE Rep...

Страница 2: ...plate Heaters that are not factory approved could cause damage and are not covered under equipment warranty INSTALLATION LIMITATIONS RECOMMENDATIONS The general location of the Air Handler is normally...

Страница 3: ...allation instruc tions These should only be installed on the supply air side of the system 23 Unit installation must include either a return air duct or grille that prevents accidental access to pins...

Страница 4: ...8 LOCATED ON LEFT SIDE 1 2 3 4 Figure 4 Two Piece Wrapper Spear Closeup NOTE Make certain that the unit has been installed in a level position to ensure proper draining UPFLOW 1 Before installing unit...

Страница 5: ...baffle See Figure 12 a Remove the factory installed baffle assembly from the apex of the coil by using a 5 16 nutdriver to remove the screws b Replace this baffle with the factory supplied nar row coi...

Страница 6: ...ckets Remove and Discard Replace with Narrow Baffle For Maximum Efficiency on Upflow Figure 12 Baffle Replacement Figure 13 Electrical Knockouts Electrical Knockout Sticker Sheet 12 After ductwork con...

Страница 7: ...Actuator Tab Electrical Contacts Electrical Contacts FIELD CHARGER COLLECTION CELL FIELD CHARGER COLLECTION CELL HORIZONTAL RIGHT Actuator Tab Electrical Contacts Electrical Contacts Figure 14 COLLECT...

Страница 8: ...cal Contacts on Bottom side FIELD CHARGER COLLECTION CELL DOWNFLOW Actuator Tab Electrical Contacts Electrical Contacts FIELD CHARGER COLLECTION CELL Downflow and Horizontal Left orientations availabl...

Страница 9: ...ation isolators field supplied must be placed under the unit 4 It is always recommended that an auxiliary drain pan be installed under a horizontal Air Handler See Condensate Drain Piping to prevent p...

Страница 10: ...utline drawing on page 21 for sizes of the duct connections After the duct is secured seal around the supply duct to prevent air leakage NOTE If the convertible duct flanges are not used they must be...

Страница 11: ...of air handler condensate drain connection Close as possible Figure 22 Field Fabricated Traps 2 MINIMUM 2 MINIMUM EZT 105 Figure 21 Manufactured Traps Figure 20 Drain Connections 3 4 NPT Primary drai...

Страница 12: ...Sup port the condensate piping and traps outside the unit to prevent strain on the drain coupling H ELECTRICAL POWER WIRING 1 These Air Handlers are shipped from the factory wired for 230 Volts The u...

Страница 13: ...ge 1 2 3 heat humidifier and EAC relays User Interface displays UNIT TEST EXIT Displayed for three seconds NOTE Airflow is default or programmed selections J AIRFLOW ADJUSTMENT Blower speed changes ar...

Страница 14: ...14 18 GE15D1 2 Installer s Guide USERINTERFACEMENU COMMUNICATINGMODE Figure 24 User Interface Menu Communicating Mode...

Страница 15: ...18 GE15D1 2 15 Installer s Guide USER INTERFACE MENU 24 VAC MODE Figure 25 User Interface Menu 24V Mode...

Страница 16: ...arge Air Sensor Open Error 6 Flash N A RAS RNG ERR N A 117 Return Air Temperature Fault Return Air Temperature Range Error RAS SHORT Return Air Sensor Short Error RAS OPEN Return Air Sensor Open Error...

Страница 17: ...ller s Guide M FIELD WIRING REFERENCE ONLY COMMUNICATING INDOOR UNIT WITH COMMUNICATING COMFORT CONTROL COMMUNICATING OUTDOOR UNIT COMMUNICATING INDOOR UNIT WITH COMMUNICATING COMFORT CONTROL 24 VAC S...

Страница 18: ...8 18 GE15D1 2 Installer s Guide COMMUNICATING INDOOR UNIT WITH 24 VAC COMFORT CONTROL 24 VAC SINGLE STAGE COOLING COMMUNICATING INDOOR UNIT WITH 24 VAC COMFORT CONTROL 24 VAC 2 STAGE OR 2 STEP COOLING...

Страница 19: ...GE15D1 2 19 Installer s Guide COMMUNICATING INDOOR UNIT WITH 24 VAC COMFORT CONTROL 24 VAC SINGLE STAGE HEAT PUMP COMMUNICATING INDOOR UNIT WITH 24 VAC COMFORT CONTROL 24 VAC 2 STAGE OR 2 STEP HEAT PU...

Страница 20: ...20 18 GE15D1 2 Installer s Guide N OUTLINE DRAWING FOR 4TEE3D01 10 Printed from D802612REV03...

Страница 21: ...000A 43 00 21 50 4TEE3D02A1000A 45 00 23 50 4TEE3D03A1000A 57 90 23 50 4TEE3D04A1000A 57 90 23 50 4TEE3D05A1000A 51 75 26 00 4TEE3D06A1000A 57 90 23 50 4TEE3D07A1000A 57 90 26 00 4TEE3D08A1000A 57 90...

Страница 22: ...CLEANING THE COLLECTION CELL 1 Turn the air conditioning system off at the Comfort Control 2 Loosen thumbscrews to remove the filter panel Remove the COLLECTION CELL by pulling for ward See Figure 5 p...

Страница 23: ...IATE GLOVES WHEN HANDLING THE FIELD CHARGER 4 Wipe down the face plate of the FIELD CHARGER with a dry shop towel or use a vacuum cleaner NOTE Do NOT disassemble the FIELD CHARGER 5 Push a block of fo...

Страница 24: ...the variable speed motor d Turn the system power ON e Turn the Comfort Control to Fan only setting f Check for LED illumination on the power supply to the air cleaner LED illumination indicates High V...

Отзывы: