 18-AD43D1-1C-EN

Installer’s Guide

d.  The recommend installation position for the TXV bulb 

is parallel to the ground (on a horizontal plane).  The 

bulb position should be at 2 o'clock or 10 o'clock.  See 

Figure 7.

e. 

Wrap the bulb and suction with field provided insulation 

after the spring clip is reinstalled.

H.  LEAK CHECK

1.  Using a manifold gauge, connect an external supply of dry 

nitrogen to the gauge port on the liquid line.  

2.  Pressurize the connecting lines and indoor coil to 150 PSIG 

maximum.

3.  Leak check brazed line connections using soap bubbles.

Repair leaks (if any) after relieving pressure.

4.  Evacuate and charge the system per the instructions packaged 

with the outdoor unit.

I.  CONDENSATE DRAIN PIPING

Condensate drain connections are located in the drain pan at 

the bottom of the coil/enclosure assembly. The female threaded 

fitting protrudes outside of the enclosure for external connection.  

A field fabricated trap is not required for proper drainage due to 

the positive pressure of the furnace; however, it is recommended 

to prevent efficiency loss of conditioned air. 

1.  The drain hole in the drain pan must be cleared of all insulation.
2.  Insulate the primary drain line to prevent sweating where 

dew point temperatures may be met. (Optional depending on 

climate and application needs)  

3.  Connect the secondary drain line to a separate drain line (no 

trap is needed in this line).

J.  CLEANING THE COIL

The two piece door allows removal of the outer casing doors 

without interference from refrigerant or condensate lines.
The foil covered insulation on 4PXC coils should be wiped down 

and residual dirt and dust should be vacuumed up to maintain 

good air quality. See Figure 8.
The manufacturer’s recommendation for coil cleaning is to initially 

use only water to wash away debris that may have collected on 

and in the coil fin surface. Removing an evaporator coil is the best 

way to effectively clean a coil that is heavily contaminated. This 

is accomplished by removing the coil from the cabinet, sealing 

the liquid and vapor line and using a strong water stream such 

as from a garden hose, being careful to prevent fin damage. Use 

chemical cleaners, only when necessary.  

NOTE:   

Refer to Service Guideline, UN-SVG001C-EN, Evaporator 

Coil Cleaning and Condensate Drain Maintenance Guide-

lines for important information on cleaning coils with 

chemical treatments.

SENSING BULB

SUCTION LINE

Bulb position at

2 o’clock or

10 o’ clock

Figure 7

Figure 8

Содержание 4PXCDU60BS3HAC

Страница 1: ...dripping into the supply ductwork NOTE 4PXC upflow coils may be installed in Upflow Downflow Horizontal Right with kit and Horizontal Left with kit 4PXC downflow coils may be installed in Downflow and...

Страница 2: ...rectly in front of the coil connections when removing sealing plugs If no pressure is released check for leaks 1 DOWNFLOW COIL CONVERSION On 4PXCDD60BS and 4PXCDU60BS installing the water diverter baf...

Страница 3: ...ber plugs from the indoor coil 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run the re...

Страница 4: ...redofallinsulation 2 Insulate the primary drain line to prevent sweating where dew point temperatures may be met Optional depending on climate and application needs 3 Connect the secondary drain line...

Страница 5: ...18 AD43D1 1C EN 5 Installer s Guide Outline Drawing for Upflow model 4PXCBU36BS3HAC 4PXCBD36BS3HDC 4PXCDU60BS3HAC 4PXCDD60BS3HDC From Dwg D346711 Rev B...

Страница 6: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is co...

Страница 7: ...18 AD43D1 1C EN 7 Installer s Guide...

Страница 8: ...plications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and sp...

Отзывы: