background image

4

18-AC51D5-5

Installer’s Guide

9. The liquid line shut-off valve can now be opened.  Remove

shut-off valve cap.  Fully insert hex wrench into the stem
and backout counterclockwise until valve stem just touches
rolled edge (approximately five [5] turns) observing

WARNING

 statement on page 2.  See Figure 4.

10. Replace liquid service pressure tap port cap and valve

stem cap.  These caps 

MUST BE REPLACED

 to

prevent leaks.  Replace valve stem cap and pressure tap
cap finger tight, then tighten an additional 1/6 turn.

11. The gas valve can now be opened.  For a ball type gas

valve, open the gas valve by removing the shut-off valve
cap and turning the valve stem 1/4 turn counterclock-
wise, using 1/4" Open End or Adjustable wrench.  See
Figure 5. For brass gas line service valve opening, follow
9 and 10 above. See Figure 4.

12. The gas valve is now open for refrigerant flow.  Replace

valve stem cap to prevent leaks. Again, these caps

MUST BE REPLACED

 to prevent leaks.  Replace valve

stem cap and pressure tap cap finger tight, then tighten
an additional 1/6 turn.  See Figure 5.

If refrigerant lines are longer than 15 feet and/or a
different size than recommended, it will be necessary to
adjust system refrigerant charge upon completion of
installation. See unit Service Facts.

F. ELECTRICAL CONNECTIONS

CAUTION

!

Three phase scroll compressors will run in reverse if
powered up with improper phasing. If the compressor is
running backwards there will be little or no difference in
suction and discharge pressure and it will make a distinct
louder sound. Reversing any two of the field installed
power leads will correct the compressor rotation. Failure to
change the power leads to correct compressor rotation
may result in compressor damage during operation.

WARNING

!

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility of
electric shock.

1. If factory leads are attached to the line side of the

terminal block, please remove and discard before attach-
ing the field power supply connections.

   2. Power wiring and grounding of equipment must comply

with local codes.

3. Power supply must agree with equipment nameplate.

4. Install a separate disconnect switch at the outdoor unit.

5. Ground the outdoor unit per local code requirements.

6. Provide flexible electrical conduit whenever vibration

transmission may create a noise problem within the
structure.

G. COMPRESSOR START UP

After all electrical wiring is complete, SET THE THERMO-
STAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR WILL NOT RUN, and apply power by
closing the system main disconnect switch.  This will activate
the compressor sump heat (where used).  Do not change the
Thermostat System Switch until power has been applied for
one (1) hour. Following this procedure will prevent potential
compressor overload trip at the initial start-up.

REFRIGERANT CIRCUIT

Liquid Pressure Too High

Liquid Pressure Too Low

Suction Pressure Too High

Suction Pressure Too Low

Liquid Refrig. Floodback TXV System

Liquid Refrig. Floodback Capillary Tube System

I.D. Coil Frosting

Compressor Runs Inadequate or No Cooling

ELECTRICAL

Compressor & O.D. Fan Do Not Start

Compressor Will Not Start But O.D. Fan Runs

O.D. Fan Won’t Start

Compressor Hums But Won’t Start

Compressor Cycles on IOL

I.D. Blower Won’t Start

SYSTEM FAULTS

P - Primary Causes      S - Secondary Causes

P

P

P

S

S

P

S

S

S

S

S

S

S

P

S

S

S

S

P

P

P

P

S

S

S

S

S

S

S

P

P

P

P

S

P

P

S

S

S

P

P

P

P

P

P

P

P

P

P

S

S

S

P

P

P

P

P

S

P

S

P

S

S

S

S

S

S

S

P

P

P

P

P

S

P

P

POWER SUPPLY

HIGH VOLTAGE WIRING

COMPR. IOL

RUN CAPACITOR

START CAPACITOR

START RELAY

CONTACTOR CONTACTS

LOW VOLTAGE WIRING

CONTROL TRANSFORMER

CONTACTOR COIL

LOW VOLTAGE FUSE

STUCK COMPRESSOR

INEFFICIENT COMPRESSOR

REFRIGERANT UNDERCHARGE

REFRIGERANT OVERCHARGE

EXCESSIVE EVAP. LOAD

NONCONDENSABLES

RESTRICTED O.D. AIRFLOW

O.D. AIR RECIRCULATION

TXV STUCK OPEN

SUPERHEAT

RESTRICTED I.D. AIRFLOW

REF. CIRCUIT RESTRICTIONS

O.D. FAN SPEED SWITCH

TROUBLESHOOTING CHART — WHAT TO CHECK

H. OPERATIONAL AND CHECKOUT

PROCEDURES

Final phases of this installation are the unit Operational and
Checkout Procedures which are found in this instruction (see
page 8). To obtain proper performance, all units must be
operated and charge adjustments made in accordance with
procedures found in the Service Facts.

I. SEACOAST SHIELD

Units installed within one mile of salt water, including
seacoasts and inland waterways, require the addition of
BAYSEAC001 (Seacoast Kit) at the time of installation.

J. TROUBLESHOOTING

Содержание 2TTA0030

Страница 1: ...an Remove tabs by cutting with a sharp tool as shown in Figure 2 see page 2 2 The unit should be set on a level support pad at least as large as the unit base pan such as a concrete slab If this is no...

Страница 2: ...E OR OUTSIDE THE STRUCTURE 4 Provide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficient length 6 Uncoil the tubing do not kink or dent 7 Route...

Страница 3: ...erant charge the gas and liquid line valves must remain closed 1 Upon completion of leak check evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves 2 Attach app...

Страница 4: ...lectrical conduit whenever vibration transmission may create a noise problem within the structure G COMPRESSOR START UP After all electrical wiring is complete SET THE THERMO STAT SYSTEM SWITCH IN THE...

Страница 5: ...grounding of equipment must comply with local codes 3 Low voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to...

Страница 6: ...28 3 4 724 28 1 2 651 25 5 8 7 8 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTA0040AD 2 2 730 28 3 4 724 28 1 2 651 25 5 8 1 1 8 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTA0050AD 3 1...

Страница 7: ...18 AC51D5 5 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 0...

Страница 8: ...X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is recommended...

Отзывы: