Installer’s Guide
Read this manual carefully before attempting to install, operate,
or perform maintenance on this unit. Installation and maintenance
should be performed by qualified service technicians only. This
unit is listed by Underwriters Laboratory.
Model WC heat pump units are designed for outdoor mounting
with a vertical condenser discharge. They can be located either
at ground level or on a roof in accordance with local codes. Each
unit contains an operating charge of refrigerant as shipped.
Extreme mounting kits are available for slab (BAYEXMK002AA)
and curb (BAYEXMK003AA) mountings.
The indoor fan motor speed tap setting is provided in the
Maintenance section.
This guide is organized as follows:
Step 1-Inspect Shipment
Step 2-Determine Unit Clearances
Step 3-Review Location and Recommendation Information
Step 4-Unit Installation
Step 5-Unit Startup
Sequence of Operation
Maintenance
Introduction
Contents
Safety Considerations
2
Introduction
3
Step 1-Inspect Shipment
3
Step 2-Determine Unit Clearances
4
Step 3-Review Location and Recommendation
Information
12
Step 4-Unit Installation
13
Ground Level Installation
13
Rooftop Installation -- Curb Mounting
13
Covert Horizontal Airflow to Down Airflow
13
Install Full Perimeter Roof Mounting Curb
13
Lifting and Rigging
13
Placing the Unit on the Mounting Curb
14
Rooftop Installation -- Frame Mounting
14
Ductwork Installation
17
Attaching Downflow Ductwork to Roof Curb
17
Attaching Horizontal Ductwork to Unit
17
Condensate Drain Piping
17
Air Filter Installation
18
Electrical Wiring
18
Electrical Connections
18
Electrical Power
18
Disconnect Switch
18
Overcurrent Protection
18
Power Wiring
18
Field Wiring Diagram
19
Control Wiring (Class II)
20
Step 5-Unit Startup
20
Pre-start Quick Checklist
20
Starting the Unit in the Cooling Mode
20
Operating Pressures
20
Voltage Check
20
Cooling Shut Down
20
Starting the Unit in Heating Mode
21
Heating Shutdown
21
Sequence of Operation
20
Demand Defrost Operation
21
Defrost Control
21
Final Installation Checklist
22
Maintenance
22
Owner Maintenance
22
Condenser Coil
22
Service Maintenance
22
Cooling Season
22
Heating Season
22
Indoor Fan Motor Speed Tap Setting
22
Warranty Information
24
Step1—Inspect Shipment
1. Check for damage after the unit is unloaded. Report
promptly to the carrier any damage found to the unit. Do not
drop the unit.
Important: To prevent damage to the sides and top of
the unit when hoisting, the use of “spreader bars” is
recommended.
2. Check the unit’s nameplate to determine if the unit is correct
for the intended application. The power supply must be
adequate for both the unit and all accessories.
3. Check to be sure the refrigerant charge has been retained
during shipment. Remove the Compressor access panel to
access the 1/4" flare pressure taps.
4. If this unit is being installed on a curb, verify that the correct
curb is provided with the unit.
•
WC~3018 through WC~3036 use the small cabinet,
Model BAYCURB050A.
•
WC~3042 through WC~3060 use the large cabinet,
Model BAYCURB051A.
5. If the unit is being hoisted, accessory kit BAYLIFT002AA is
recommended. It includes a kit of four (4) lifting lugs and
instructions.