background image

18-GE09D1-9

9

Installer’s Guide

The indoor blower is downstream of the evaporator coil
which creates a negative pressure at the condensate
drain connections during operation. The condensate
drain connections in front of the indoor coil are 3/4"
NPT. The lower connection is the primary drain. See
Figure 14.

Two secondary drain connections are provided for the
different orientations (See Figure 14). The lower of the
two should be connected as a backup to prevent conden-
sate overflow by a blocked primary drain. The weep
hole in center of drain coupling area should be sealed
with caulk or RTV except in downflow unless secondary
drain is connected.

For proper drainage of condensate, the following steps
should be followed:

1. The primary drain line must be trapped with a mini-

mum of 2" water seal as shown in Figures 15 & 16.

Do not use preformed 3/4" PVC running traps.

The use of Field fabricated or manufactured traps
as shown in Figures 15 & 16 is acceptable. The
manufactured trap shown in Figure 8 allows for a
float switch option to be added. Refer to the
manufacturer’s data and instructions for details.

2. The trap must be located within 4 feet of the air

handler drain outlet connection.

3. It is recommended that a clean-out tee or cross

be installed in the primary drain line for future
maintenance (See Figures 15 & 16)

4. Do not use reducing fittings in the condensate

drain lines.

2. Field supplied tubing should be cut square, round

and free of burrs at the connecting end. Clean the
tubing to prevent contaminants from entering the
system.

3. Run refrigerant tubing into the stub sockets of in-

door unit coil.

4. Braze and evacuate according to indoor and outdoor

installation instructions.

5. Seal around refrigerant lines.

PAINTED AREAS OF UNIT MUST BE SHIELDED
DURING BRAZING.

G. CONDENSATE DRAIN PIPING

NOTE: Make certain that the unit has been installed in a
level position to ensure proper draining.

r

5. Slope the drain lines downward a minimum of 1/4"

per foot.

6. Insulate the primary drain to prevent sweating

where dew point temperatures may be met.

7.

Provide means for drainage to prevent winter
freeze-up of condensate line

.

8. Do not connect the drain line to a closed drain sys-

tem.

9. Use Teflon

®

 tape on the air handler drain line

connections!  Do Not Use pipe joint compound or
PVC/CPVC cement!

It is always recommended that an auxiliary drain pan
be installed under a horizontally installed air handler.
Connect the auxiliary drain line to a separate drain line
(no trap is needed in this line) and terminate according
to local codes.

NOTE: DO NOT use a torch or flame near the plastic
drain pan coupling.

NOTE: DO NOT tighten the drain pipe excessively. Sup-
port the condensate piping and traps outside the unit
to prevent strain on the drain coupling.

BRAZE SHIELD

e

3/4" NPT
Primary drain
connection

3/4" NPT

Secondary

drain

connection

Seal weep
hole except
for Downflow
configuration

Содержание 2/4TEH3F18B1000A

Страница 1: ...s do not cover all variations in systems or provide for every possible contingency Should fur ther information be desired or particular problems arise which are not covered sufficiently by this manual con tact your local distributor or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are full...

Страница 2: ...if the minimum clearances to combustible materials and service access are observed the above installations are suitable This area may also be used for other purposes includ ing an electric hot water heater but in no case shall a fossil fuel device be installed and or operated in the same closet alcove or utility room In addition these air handlers are suitable for installa tion in an attic garage ...

Страница 3: ... width requirements must be considered in the overall space needed 17 These units are not approved for outdoor installa tion 18 These units are approved for draw through appli cation only NOTE No atomizing style humidifier is allowed in the return plenum with the use of this unit 19 Flow through Bypass Humidifiers Excessive bypass air may cause water blow off which will adversely affect system ope...

Страница 4: ... as shown in the outline drawing e On units with sheetmetal returns Return ple num should be flanged Sheetmetal screws must be 1 2 in length or shorter f No sheetmetal screws may be used to attach re turn duct work on the side of the unit g Pedestal and unit should be isolated from the foundation using a suitable isolating material h Openings where field wiring enters the cabinet must be completel...

Страница 5: ...ll the baffle to coil with gasket material compressed against the coil f Install the water blow off baffles provided on each side of the coil with the flange at the top as shown in Figure 9 The bottom of the baffle is to be as close to the bottom of the coil as possible g Install the 7 8 wide gasket in each side of the drain pan as shown in Figure 9 h Place the 2 water diverter baffles 5 ton model...

Страница 6: ...should not ex ceed the face velocity of the filter being used The factory installed filter should then be removed from the unit Remove the factory installed baffle assembly from the apex of the coil by using a 5 16 nutdriver to remove the hex head screws Replace this baffle with the factory supplied narrow coil baffle using the screws re moved previously See Figure 5 CAUTION When installing the na...

Страница 7: ...revent sagging The service access must remain unobstructed If the unit is sup ported along the length of the front and back with rails the air handler only needs to be sus pended at both ends See Figure 10 with rails the air handler only needs to be sus pended at both ends See Figure 10 If the unit is not suspended it must be supported as mentioned above and isolated carefully to pre vent sound tr...

Страница 8: ...prevent air leakage NOTE No sheetmetal screws may be used to attach re turn ductwork on the side NOTE On units with sheetmetal returns Return plenum should be flanged Sheetmetal screws must be 1 2 in length or shorter See Figure 12 NOTE If the convertible duct flanges are not used they must be removed and discarded for proper airflow NOTE Any duct board return connection can be made to the sides o...

Страница 9: ...g fittings in the condensate drain lines 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run refrigerant tubing into the stub sockets of in door unit coil 4 Braze and evacuate according to indoor and outdoor installation instructions 5 Seal around refrigerant lines PAINTED AREAS OF UNIT M...

Страница 10: ...e as well as any other cabinet penetrations must be sealed air tight I CONTROL WIRING 1 Connect wiring between indoor unit outdoor unit and Comfort Control The use of color coded low voltage wires is recommended 2 Field wiring diagrams are provided which show the low voltage wiring hook up for a single speed cooling only system with supplementary heaters and a heat pump system with supplementary h...

Страница 11: ...18 GE09D1 9 11 Installer s Guide 2 4TEH AIR HANDLER WITH HEAT PUMP WITH SUPPLEMENTAL HEAT From Dwg B801082 Rev 2 ...

Страница 12: ...12 18 GE09D1 9 Installer s Guide 2 4TEH AIR HANDLERS WITH SINGLE SPEED COOLING UNIT 1 STAGE HEAT From Dwg B801083 Rev 2 ...

Страница 13: ...18 GE09D1 9 13 Installer s Guide 2 4TEH AIR HANDLER WITH SINGLE SPEED COOLING UNIT 2 STAGE HEAT From Dwg B801081 Rev 2 ...

Страница 14: ...14 18 GE09D1 9 Installer s Guide OUTLINE DRAWING FOR 2 4TEH3F18 60B ...

Страница 15: ...R HANDLER DIMENSIONAL DATA MODEL H W 2 4TEH3F18B 43 00 21 50 2 4TEH3F24B 43 00 21 50 2 4TEH3F30B 45 00 21 50 2 4TEH3F36B 45 00 21 50 2 4TEH3F42B 51 75 23 50 2 4TEH3F48B 57 90 23 50 2 4TEH3F60B 57 90 23 50 2 4TEH3F48B 60B Are two piece cabinets ...

Страница 16: ...th code 3 Make sure unit suspension if used is secure and that there are no tools or loose debris in around or on top of the unit 4 Check all duct outlets they must be open and unrestricted 5 Check drain lines and be sure all joints are tight 6 Make sure secondary drain pan is installed 7 Check power supply for correct requirements per unit nameplate 8 Check filters for proper size Inform owner of...

Отзывы: