56
4T-V0-SF-1Q-EN
Technician Control Menu
Forced Defrost, EEV, LSOV, Evacuation, Run Drive and
Run Outdoor Fan tests are initiated and performed
from the Technician Control Menu.
N
No
otte
e:: If system is in Lockout, Unit Tests are not
available.
CONTROL MENU
CONFIG
MENU
MONITOR
MENU
RUN OD FAN?
PRESS ENTER
MOTOR PWM
XX
STOP OD FAN?
PRESS ENTER
Run OD Fan Test Notes
1. System can be in any mode but must be idle to
enter RUN OD FAN test.
2. If thermostat is sending demand to the outdoor
unit, RUN OD FAN test is not available.
3. Press ENTER from RUN OD FAN screen.
4. Send 99% PWM (100%CFM) to OD Fan Motor.
5. When test begins, change screen to display
“MOTOR PWM” on line 1 and actual PWM value
on line 2.
6. To end test, navigate to right and press ENTER
from STOP OD FAN screen.
7. User should be able to navigate back and forth
between the display screen and the STOP OD
FAN screen.
8. Test terminates after 1 hour if STOP OD FAN
step is not use.
Run OD Fan Test Procedure
The OD Fan Test sends a high-speed
command signal to the OD fan motor
and can be used to verify motor and
control operations.
If the OD Fan motor does not run:
1. Verify fan blades are free from obstruction
and motor turns freely.
2. Confirm high voltage to OD Fan is present
and in range (187VAC-252VAC).
3. Confirm high voltage leads are connected
and not damaged.
4. Confirm motor is receiving a PWM signal
by measuring DC Volts at plug J9 on the
IVCS. High speed fan signal should
measure between 15-18 Volts DC.
5. Confirm PWM motor plug (J9) and leads
are connected and not damaged.
With all inputs and conditions verified,
motor is defective.
RUN DRV TEST
PRESS ENTER
SHORTED
WIRE/WINDING
NO FAULT
OPEN
WIRE/WINDING
TESTING
PASSED
FAILED
LOCKED ROTOR
Drive Test Notes
1. Drive Diagnostics forces a shutdown and waits
until compressor is completely coasted before
running the drive diagnostic routine.
2. The OD system will enter a hard lockout state to
ensure no other system component is attempting
to run.
3. Show “TESTING” while internal diagnostics are
being performed (about 30 seconds).
4. One of five conclusions will be displayed at the
end of the Drive Test as a result of running the
test.
5. At the conclusion of this test, the results screen
will remain displayed until power is cycled or the
Exit Drive Test option is used.
6. If Drive Test result is “Passed No Fault” the
compressor will run for one minute.
7. The user will then have the ability to scroll up or
down to visit an Exit Drive Test screen. Exiting the
Drive Test will reset the IVSC software and clear
the hard lockout state.
8. If the Drive Diagnostic test is not exited, a 2 hour
timer will be kept, and upon expiration of that
timer the IVSC will automatically reset itself.
FAILED
DRIVE HW
EXT DRV TST
PRESS ENTER
continued on next page