CLCH-SVX009J-EN

11 

Pre-Installation

Receiving and Handling

Inspection

Upon delivery, thoroughly inspect all components for any 
shipping damage that may have occurred, and confirm 
that the shipment is complete. See the Receiving Checklist 
section below for detailed instructions.

Note:

Delivery cannot be refused. All units are shipped 
F.O.B. factory. Trane is not responsible for shipping 
damage.

Packaging/Shipping

Performance air handlers ship as a complete unit or in 
individual sections to be field assembled. Indoor air 
handler sections are stretch-wrapped before shipping. All 
factory shipping protection should be removed upon 
delivery. This wrapping is for transit protection only.

Outdoor Performance air handlers are not wrapped, but 
openings are covered to comply with LEED EQ Credit 5.

Smaller components and hardware may be shipped 
separately, or shipped inside the unit. This hardware is 
typically packaged in a clear plastic envelope or cardboard 
box, and can be found inside the fan or mixing box.

Identification

Each air handler section includes a nameplate identifying 
the section type and functional components, customer 
tagging information, unit serial number, unit order 
number, the build-section position for installation, and the 
unit model number. See 

“Nameplate,” p. 5.

Handling

Indoor air handlers sizes 3-30 are shipped with a shipping 
skid designed for forklift transport.

Outdoor air handlers have an integral base frame 
designed with the necessary number of lift points for safe 
installation. Se

“Lifting and Rigging,” p. 20

.

Receiving Checklist

Complete the following checklist immediately after 
receiving shipment to detect possible shipping damage.

Jobsite Storage

Indoor air handlers and field-installed accessories must be 
protected from the elements. A controlled indoor 
environment is recommended for proper storage. 

Note:

All factory shipping protection should be removed, 
This wrapping is for transit protection only.

The unit controller and all other electrical/electronic 
components should be stored in conditions of -20°F to 
120°F and 5 to 95 percent relative humidity, non-
condensing. Electrical components are not moisture-
tolerant. 

Outdoor units require no special protection for storage 
prior to installation.

Check to ensure that the shipment is complete. Small 
components may ship inside the unit or ship 
separately. Check the parts list to ensure all materials 
are present. If any component is missing, contact your 
local Trane sales office.

Check all units, components, connections, and piping. 
Check fan wheel for free rotation by spinning 
manually. Check all doors, latches and hinges. Inspect 
interior of each unit or section. Inspect coils for 
damage to fin surface and coil connections. Check for 
rattles, bent corners, or other visible indications of 
shipping damage. Tighten loose connections.

If a unit is damaged, make specific notations 
concerning the damage on the freight bill. Do not 
refuse delivery.

Notify the carrier’s terminal of the damage 
immediately by phone and mail. Request an 
immediate joint inspection of the damage by the 
carrier and consignee.

Notify your Trane sales representative of the damage 
and arrange for repair. Do not attempt to repair the unit 
without consulting the Trane representative.

Inspect the unit for concealed damage as soon as 
possible after delivery. Report concealed damage to 
the freight line. It is the receiver’s responsibility to 
provide reasonable evidence that concealed damage 
did not occur after delivery. Take photos of damaged 
material if possible.

Note:

Concealed damage must be reported within 15 
days of receipt.

Содержание Climate Changer UCCA

Страница 1: ...30 SAFETY WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous a...

Страница 2: ...hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment o...

Страница 3: ...ble electric heat voltage ratings in electrical requirements chapter Updated typical VFD wiring schematic for indoor and outdoor air handlers in the electrical requirements chapter Updated typical dua...

Страница 4: ...ent and Assembly for Indoor Air Handlers 24 Unit Placement and Assembly for Outdoor Air Handlers 30 Duct Connections 35 Field Conversions 36 Coil Piping and Connections 38 General Recommendations 38 D...

Страница 5: ...at identifies the type of section and functional components customer tagging information the unit serial number the unit order number the build section position for installation and the unit model num...

Страница 6: ...are acceptable for ambient temperatures up to 104 F while motors with Class F insulation can withstand ambient temperatures to 140 F 60 C Note Units with UL approval have a maximum ambient temperature...

Страница 7: ...for field provided controls Various end device options including Low limit protection Condensate overflow switch Fan status switch Filter status switch Discharge air sensor Mixed air sensor Return air...

Страница 8: ...fpi T 8 row hydronic coil 14 fpi U 4 row DX coil 9 fpi V 4 row DX coil 12 fpi W 4 row DX coil 14 fpi Y 6 row DX coil 9 fpi Z 6 row DX coil 12 fpi 1 6 row DX coil 14 fpi S Special Digit 14 Unit Coil 2...

Страница 9: ...fixed 850 950 variable G 950 rpm fixed 900 1000 variable H 1000 rpm fixed 950 1050 variable J 1050 rpm fixed 1000 1100 variable K 1100 rpm fixed 1050 1150 variable L 1150 rpm fixed 1100 1200 variable...

Страница 10: ...at filter with back return single point power 8 2 in angle filter with back return single point power 9 2 in 4 in combination filter with back return single point power S Special Digit 29 Filter type...

Страница 11: ...dlers and field installed accessories must be protected from the elements A controlled indoor environment is recommended for proper storage Note All factory shipping protection should be removed This...

Страница 12: ...free air and necessary service access see Service Clearances p 14 Refer to submittals for specific minimums Allow room for supply and return piping ductwork electrical connections and coil removal Ens...

Страница 13: ...al clearances 3 Remove any twist within the curb due to roof supports and square the curb 4 Level the curb 5 Secure the curb to the roof support members 6 Install 2 in thick boards or rigid insulation...

Страница 14: ...66 00 66 00 C Fan Access return section motor side 48 00 48 00 48 00 51 00 54 00 58 00 61 00 61 00 66 00 66 00 D Control Box 56 00 56 00 56 00 56 00 56 00 56 00 56 00 56 00 56 00 56 00 E VFD 48 00 48...

Страница 15: ...56 00 56 00 56 00 D Return Fan Door 48 00 48 00 48 00 51 00 54 00 58 00 61 00 61 00 66 00 66 00 E Filter mixing box economizer opposite coil connection side 30 00 34 00 32 00 32 00 30 00 35 00 35 00 3...

Страница 16: ...8 70 78 70 80 20 84 30 84 30 87 00 93 60 Coils Hydronic DX coils galvanized and stainless steel casing Area ft2 2 80 5 60 7 60 9 90 12 30 14 30 16 30 20 40 24 00 28 50 Width in 17 50 22 50 27 50 27 50...

Страница 17: ...6 90 8 90 11 10 16 30 16 30 20 00 22 50 26 40 30 60 Nominal Velocity fpm 432 0 432 0 450 0 450 0 369 2 430 8 425 0 466 7 473 7 490 9 2 in Angle Filter 16 x 20 2 6 6 6 4 12 16 x 25 2 3 3 8 20 x 20 4 2...

Страница 18: ...46 164 44 125 00 161 00 241 00 160 00 17 133 09 172 89 160 00 256 00 241 00 125 00 21 155 81 290 14 196 00 n a 256 00 125 00 25 168 83 304 07 196 00 256 00 n a 250 00 30 208 34 317 00 250 00 322 00 n...

Страница 19: ...00 15 20 15 22 00 27 230 V 60 Hz 3 PH 8 60 1800 15 20 15 22 00 27 460 V 60 Hz 3 PH 4 20 1800 4 80 12 11 00 20 575 V 60 Hz 3 PH 3 30 1800 3 90 20 9 00 25 5 200 V 60 Hz 3 PH 15 70 1800 22 00 22 42 00 31...

Страница 20: ...FC Fan 3 10 1 Removescrewsattachingshippingprotectionbrackets from center of isolation base to casing mounting bracket 2 Remove shipping protection brackets through door Figure 5 Shipping tie down re...

Страница 21: ...il ready to place the unit in its permanent location Figure 9 Shipping tie down removal for FC fan 12 30 Figure 10 Shipping tie down removal for DDP fan See Detail B Detail B See Detail C Detail C NOT...

Страница 22: ...from the top of the unit WARNING Risk of Unit Dropping Failure to follow instruction below could result in death or serious injury To prevent modules subassemblies from dropping ALWAYS place assemble...

Страница 23: ...should be used for larger units where forks cannot extend under both base rails Lifting Outdoor Units Note For outdoor air handlers preparation of the roof curb or pier mount and roof openings must be...

Страница 24: ...lers If the air handler is ordered with a mixing box or angle filter section it will arrive in sections Some assembly may be required For details see Section assembly see Unit Assembly for Indoor Unit...

Страница 25: ...frame can be mounted parallel to airflow or perpendicular to airflow WARNING Toxic Fumes Keep open flame away from unit exterior or interior Do not weld or use cutting torch on the exterior or interi...

Страница 26: ...Base Frame If a factory provided integral base frame is used for ceiling suspension the individual sections and or subassemblies will have base frame shipping splits and base frame lifting lugs While...

Страница 27: ...eld provided wiring Consider overall unit serviceability and accessibility before mounting running wires power making cabinet penetrations or mounting any components to the cabinet Joining at Shipping...

Страница 28: ...o a tight space the second level fan section of a vertical unit can be removed to maneuver the unit into the space Removal will require field supplied lifting lugs part LUG00180 1 Remove screws Item 2...

Страница 29: ...a control interface VFD or electric heat disconnect electrical wiring Wiring between fan motor and contactor or VFD can be disconnected via quick connects in the control interface or VFD box respecti...

Страница 30: ...perimeter of the unit Both the unit and the pipe cabinet should be supported by their base channel around the entire perimeter see Figure 32 and Figure 33 Assembly If a unit arrives in sections then e...

Страница 31: ...ack of pipe cabinet side wall full height of the side wall along the outer edge to base and roof full length of the roof along the outer edge and peel off the liner Strips of tape must contact each ot...

Страница 32: ...rews mount the weather hoods to the unit 4 Units withmultiple intakehoodsrequire that the hoods be installed from bottom to top Overlap locations should be sealed with butyl caulk between the hoods No...

Страница 33: ...Installation Mechanical CLCH SVX009J EN 33 Figure 36 Intake hood installation Butyl caulk tape 1 00W x 0 125T Butyl caulk tape 1 00W x 0 125T Screw self drille 0 250 14 x 0 7 Intake hoods...

Страница 34: ...5 20 25 20 20 20 20 25 16 25 16 20 16 20 16 Size 25 26 40 ft 20 25 20 25 20 25 20 25 20 25 20 25 25 16 25 16 Size 30 30 60 ft 20 25 20 25 20 25 20 25 25 16 25 16 25 16 25 16 25 16 25 16 Size 17 20 00...

Страница 35: ...back up into the drain pan causing it to overflow See Drain Pan Trapping p 38 Fan Discharge Connections To ensure the highest fan efficiency duct turns and transitions must be made carefully minimizin...

Страница 36: ...hat secure the coil to the cabinet roof Remove the screws that attach the roof to the side walls and the front panel 4 Remove roof 5 If horizontal front or back discharge loosen and remove j bolt secu...

Страница 37: ...djust the isolators to achieve the proper operation height of the fan and motor isolation base Minimum required clearances are listed in Table 7 To determine the isolator clearances on all unit sizes...

Страница 38: ...ain pan for cleaning purposes only it does not need a trap however a cap or shutoff valve should be installed on the drain connection Only sections handling condensate such as a cooling coil section o...

Страница 39: ...egative pressure L H J pipe diameter where H 1 inch for each inch of negative pressure plus 1 inch J 1 2 H Section under positive pressure L H J pipe diameter where H 1 2 inch minimum J 1 2 inch plus...

Страница 40: ...de of the trap 4 If installing coils in series airflow control each coil bank independently with an automatic steam control valve Size the traps for each coil using the capacity of the first coil in d...

Страница 41: ...ty is below these minimums vent the coil by one of the following methods 1 Install an air vent in the top pipe plug tapping of the return header 2 When the return line rises above the top of the coil...

Страница 42: ...tailed schematics of evaporator piping Figure 49 Example of placement for split system components Discharge line Manual ball valve Access port Filter Access port Access port Filter drier with access p...

Страница 43: ...t systems with mircochannel heat exchanger condensers MCHE solenoid valves isolate the refrigerant from the evaporator during the off cycles Trim solenoids cannot be used with MCHE Note Trane condensi...

Страница 44: ...installed after the system is cleaned up Access port The access port is used to determine suction pressure This port is usually a Schraeder valve with a core Frostat coil frost protection The Frostat...

Страница 45: ...suitable for use with R 410A These same lines sized at 1 5 8 OD or 2 1 8 OD must use type K or thicker wall Expansion valves need to be reselected Expansion valves are refrigerant specific Any gasket...

Страница 46: ...ader connection 4 Use the tube diameter recommended in the condensing unit application manual for a vertical rise Ensure that the top of the riser is higher than the evaporator coil 5 Pitch the suctio...

Страница 47: ...Use the tube diameter recommended for a vertical rise as specified in the condensing unit application manual Assure the top of the riser is higher than the evaporator coil 7 Pitch the suction line sl...

Страница 48: ...meter recommended for a vertical rise as specified in the condensing unit application manual Ensure that the top of the riser is higher than the evaporator coil 7 Pitch the suction line slightly 1 in...

Страница 49: ...a vertical rise as specified in the condensing unit application manual 5 The top of the Circuit 2 suction riser must be higher than the top evaporator coil Use the tube diameter recommended for a vert...

Страница 50: ...as specified in the condensing unit application manual Ensure that the top of the riser is higher than the evaporator coil 7 Pitch the suction line slightly 1 in 10 feet so that the refrigerant drains...

Страница 51: ...circuit Ground loops can affect the measurement accuracy of the controller Allinput output circuits except isolated relay contacts and optically isolated inputs assume a grounded source either a groun...

Страница 52: ...ents Line voltage 24 Vac Transformer Termination board Table 11 Electric heat voltage ratings Unit Voltage Heater Voltage 200 200 230 230 460 460 575 575 Table 12 Electric heat kW limits min max Motor...

Страница 53: ...COPIED OR ITS CONTENTS DISCLOSED TO OUTSIDE PARTIES WITHOUT THE WRITTEN CONSENT OF TRANE DRAWN BY DATE DO NOT SCALE PRINT X XX XXX THIRD ANGLE PROJECTION c B B B UNLESS OTHERWISE SPECIFIED ALL DIMENSI...

Страница 54: ...ITTEN CONSENT OF TRANE DRAWN BY DATE DO NOT SCALE PRINT X XX XXX THIRD ANGLE PROJECTION c B B B UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN INCHES TOLERANCE ANGLES B HOLE DIA CONFORMS TO ASME Y14...

Страница 55: ...TTEN CONSENT OF TRANE DRAWN BY DATE DO NOT SCALE PRINT X XX XXX THIRD ANGLE PROJECTION c B B B UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN INCHES TOLERANCE ANGLES B HOLE DIA CONFORMS TO ASME Y14...

Страница 56: ...WRITTEN CONSENT OF TRANE DRAWN BY DATE DO NOT SCALE PRINT X XX XXX THIRD ANGLE PROJECTION c B B B UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN INCHES TOLERANCE ANGLES B HOLE DIA CONFORMS TO ASME Y...

Страница 57: ...N CONSENT OF TRANE DRAWN BY DATE DO NOT SCALE PRINT X XX XXX THIRD ANGLE PROJECTION c B B B UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN INCHES TOLERANCE ANGLES B HOLE DIA CONFORMS TO ASME Y14 5M...

Страница 58: ...WRITTEN CONSENT OF TRANE DRAWN BY DATE DO NOT SCALE PRINT X XX XXX THIRD ANGLE PROJECTION c B B B UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN INCHES TOLERANCE ANGLES B HOLE DIA CONFORMS TO ASME...

Страница 59: ...brication if necessary See Fan Bearing Lubrication p 73 Coil Related Checks Ensure coil and condensate drain piping connections are complete Check the piping and valves for leaks Open or close the val...

Страница 60: ...ltage imbalance is 2 percent Voltage imbalance is defined as 100 times the sum of the deviation of the three voltages from the average divided by twice the average voltage For example if the three mea...

Страница 61: ...plate 1 22 Motor Voltage Depends on unit Set Based on Motor Nameplate 1 24 Motor Current Depends on unit Set Based on Motor Nameplate 1 25 Rated Motor Speed Depends on unit Set Based on Motor Nameplat...

Страница 62: ...5 Determine actual deflection by depressing one belt with the belt tensiometer and measuring the deflection relative to the other belts or to belt line see Figure 66 Adjust the belt tension to the cor...

Страница 63: ...4 8 5 12 6 2 501 4 000 6 0 8 9 7 3 10 9 C CX 7 0 9 0 500 1 740 11 5 17 0 14 7 21 8 1 741 3 000 9 4 13 8 11 9 17 5 9 5 16 0 500 1 740 14 1 21 0 15 9 23 5 1 741 3 000 12 5 18 5 14 6 21 6 D 12 0 16 0 200...

Страница 64: ...as required After realignment tighten the belts again to the standard belt tensioning specifications If the force is still not the same for all belts the belts or sheaves are worn and must be replaced...

Страница 65: ...e in running condition and unusual noise Every month Clean or replace air filters if clogged or dirty coat permanent filters with oil after cleaning change bag filters when pressure drop is 1 in wg Se...

Страница 66: ...electric power including remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized Secure rotor to ensure rotor cannot freewhe...

Страница 67: ...angle of 15 degrees Spray perpendicular to the coil face Keep the nozzle at least 6 inches from the coil Do not exceed 600 psi 7 Spray the leaving air side of the coil first then the entering air sid...

Страница 68: ...ystem during startup If draining is questionable because of dirt or scale deposits inside the coil fill the coil with glycol before the heating season begins Note On many unit sizes there are multiple...

Страница 69: ...bleach and water solution or an EPA approved sanitizer specifically designed for HVAC use 6 Immediately rinse the affected surfaces thoroughly with fresh water and a fresh sponge to prevent potential...

Страница 70: ...orized impeller fan access through coil door Horizontal units equipped with a direct drive plenum fan the low limit switch can be accessed through the fan access door For sizes 3 6 10 and 12 see Figur...

Страница 71: ...Removable access panel Screw 10 16 x 0 750 self driller Remove all from perimeter panel Panel removed from unit Low limit freeze stat Detail A Figure 75 Resetting low limit switch for horizontal DDP...

Страница 72: ...ated materials and cleaning solution Bearing Set Screw Alignment Align bearing set screws for belt drive fans as illustrated in Figure 76 See Table 17 p 64 for set screw torque measurements Torque Req...

Страница 73: ...tions so please obtain the motor IOM and use the manufacturer recommended grease Fan Motor Inspection Inspect fan motors periodically for excessive vibration or temperature Operating conditions will v...

Страница 74: ...wer company for adjustments Mechanical failure Check that motor and drive rotate freely Check bearing lubricant Motor stalls Open phase Check line for an open phase Overloaded motor Reduce load or rep...

Страница 75: ...ce see Coils p 66 Do not use steam to clean refrigerant coils Fin frosting Verify defrost cycle operation Verify frostat operation Verify refrigerant charge Low steam coil capacity Incorrect airflow C...

Страница 76: ...re committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial a...

Отзывы: