Installer’s Guide
Wiring Start Control Kit Components
1. Connect the color coded start control wires with quick
connect ¼” flag terminals to the contactor and capacitor
as illustrated in Figure 4.
2. Route all three high voltage wires through field-supplied
½” conduit.
3. Secure field-supplied liquid tight conduit fittings at
enclosure and control box entries.
4. Attach the warning label to the enclosure cover. This
label provides a warning for hazardous voltage.
5. Re-connect power, which was disconnected in Step 1.
FIGURE 4
Red Wire:
Start Capacitor
to MS-T1
Orange Wire:
CSR 2 to Run
Capacitor -
H Terminal
Black/Blue
Wire: CSR 5
to MS-T2
Brown Wire:
Start Capacitor
to CSR 1
MS-T1
MS-T2