WSHP-SVX02C-EN

General Information

WARNING

Fiberglass Wool!

Product contains fiberglass wool. Disturbing the 
insulation in this product during installation, 
maintenance or repair will expose you to airborne 
particles of glass wool fibers and ceramic fibers known 
to the state of California to cause cancer through 
inhalation. Glass wool fibers may also cause 
respiratory, skin or eye irritation.

Jobsite Inspection 

Always perform the following checks before accepting a 
unit:

Verify that the nameplate data matches the data on the 
sales order and bill of lading (including electrical data).

Verify that the power supply complies with the unit 
nameplate specifications.

Visually inspect the exterior of the unit, for signs of 
shipping damage. Do not sign the bill of lading 
accepting the unit(s) until inspection has been 
completed. Check for damage promptly after the 
unit(s) are unloaded. Once the bill of lading is signed at 
the jobsite, the unit(s) are now the property of the 
SOLD TO party and future freight claims MAY NOT be 
accepted by the freight company.

Verify that the refrigerant charge has been retained 
during shipment by use of gauges. Access fittings are 
located internal to the cabinet on the 5-ton through 20-
ton equipment. 

After assuring that charge has been retained, reinstall 
the caps to assure that refrigerant leakage does not 
occur.

CAUTION

Microbial Growth!

Wet interior unit insulation can become an 
amplification site for microbial growth (mold), which 
may cause odors and damage to the equipment and 
building materials. If there is evidence of microbial 
growth (mold) on the interior insulation, the insulation 
should be removed and replaced prior to operating the 
system. 

Jobsite Storage

This unit is intended for indoor use only. To protect the unit 
from damage due to the elements, and to prevent possible 
IAQ contaminant sources from growing, the unit should be 
stored indoors. If indoor storage is not possible, the 
following provisions for outdoor storage must be met:

Place the unit(s) on a dry surface or raise above the 
ground to assure adequate air circulation beneath the 
unit.

Cover the unit(s) with a waterproof tarp to protect them 
from the elements.

Make provisions for continuous venting of the covered 
units to prevent moisture from standing on the unit(s) 
surfaces. Wet interior unit insulation can become an 
amplification site for microbial growth (mold) which 
has been determined to be a cause of odors and 
serious health related indoor air quality problems.

Store units in the normal UP orientation to maintain oil 
in the compressor.

Do not stack more than three units in total height for 
the EXWE 5 and 10-ton configurations, and no more 
than two units high for the EXWE configuration.

Unit Nameplate

The unit nameplate is located at the front of the unit. It 
includes the unit model number, serial number, electrical 
characteristics, refrigerant charge, and other pertinent unit 
data.

Compressor Nameplate

The nameplate for the compressors are located on the 
compressor shell.

Unit Description

Before shipment, each unit is leak tested, dehydrated, 
charged with refrigerant and run tested for proper control 
operation. 

Water-to-Refrigerant Coils

The water-to-refrigerant heat exchangers are an inner 
copper tube or cupro-nickel (option available on the 
source-side only) and steel tube (tube-within-a-tube) 
design and are leak tested to assure there is no cross 
leakage between the water and refrigerant gas.

Water Connections

Water connections are located inside the unit and are 
accessible from the back of the unit. The fitting is a female 
pipe threaded connection. The size of the connection is 1” 
for the 5 ton, 1½” for the 10 ton and 2” for the 20 ton unit.

Controls

The control system offered to control the unit is a deluxe 
24 volt micro processing board.

All power wiring to the equipment is made at the power.

All low voltage wiring is made at the unit’s low voltage 
terminal board.

Wiring Connections

Troubleshooting and connection diagrams for the 
equipment may be located in the back of this manual.

Содержание Axiom EXW

Страница 1: ...installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equi...

Страница 2: ...ted or unsaturated HFCs and HCFCs Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment our customers and the air condition...

Страница 3: ...put on all PPE in accordance with OSHA NFPA 70E or other country specific requirements for arc flash protection PRIOR to servicing the unit NEVER PERFORM ANY SWITCHING DISCONNECTING OR VOLTAGE TESTING...

Страница 4: ...ning and Flushing the Water Loop 13 Using Antifreeze 14 Field Installed Power Wiring 14 Main Unit Power Wiring 14 Control Power Transformer 15 Electrical 16 Pre Start 17 Pre Start up Checklist 17 Unit...

Страница 5: ...s not possible the following provisions for outdoor storage must be met Place the unit s on a dry surface or raise above the ground to assure adequate air circulation beneath the unit Cover the unit s...

Страница 6: ...essary terminals for field connection The deluxe board is equipped with a random start relay anti short cycle timer brown out protection compressor disable unit safety control diagnostics and a generi...

Страница 7: ...0 1 3 208 60 3 4 460 60 3 8 230 60 3 Digit 9 Heat Exchanger Source Side 1 Copper Water Coil 2 Cupro Nickel Water Coil Note Heat Exchanger for the Load Side is Copper Water Coil ONLY Digit 10 Current D...

Страница 8: ...3 EXWE240 1222 1156 Unit Location and Clearances Locate the unit in an indoor area The ambient temperature surrounding the unit must not be less than 45 F Do not locate the unit in areas subject to fr...

Страница 9: ...Figure 2 EXWE060 Dimensions and Clearances WSHP SVX02C EN 9...

Страница 10: ...Figure 3 EXWE120 Dimensions and Clearances 10 WSHP SVX02C EN...

Страница 11: ...Figure 4 EXWE240 Dimensions and Clearances WSHP SVX02C EN 11...

Страница 12: ...local codes Low Voltage Wiring Requirements 9 Connect properly sized control wiring to the proper termination points between the field supplied thermostat and the terminal strip located in the equipm...

Страница 13: ...ormerly occupied by the air that is bled off 3 With the air vented and the water circulating the entire system should be checked for leaks with repairs made as required 4 Operate the supplementary hea...

Страница 14: ...s Pipe Gallons per 100 Ft Minimum Flush GPM PE 3 02 3 8 1 PE 4 73 6 0 1 PE 7 55 9 5 1 PE 9 93 13 0 2 PE 15 36 21 0 Field Installed Power Wiring WARNING Hazardous Voltage Disconnect all electric power...

Страница 15: ...ductors Distance from unit to control Recommended wire size 000 460 feet 18 gauge 461 732 feet 16 gauge 733 1000 feet 14 gauge Table 5 Deluxe controller diagnostic LEDs Color Green Color Red LED1 LED2...

Страница 16: ...60 1 207 254 27 6 27 6 158 0 1 34 5 60 208 60 3 187 229 18 1 18 1 137 0 1 22 6 40 460 60 3 414 506 9 0 9 0 62 0 1 11 3 20 230 60 3 207 254 18 1 18 1 137 0 1 22 6 40 EXWE120 208 60 1 197 229 55 2 27 6...

Страница 17: ...rigerantheatexchanger along with air purging from the water to refrigerant heat exchanger be done in accordance with the Closed Loop Ground Source Heat Pump Systems Installation Guide Is vibration iso...

Страница 18: ...ircuit 4 Check the cooling refrigerant pressures against values in Operating Data p 19 5 Turn the system control switch to the OFF position Unit should stop running and the reversing valve should de e...

Страница 19: ...13 15 0 11 1 9 11 117 135 232 296 10 0 4 1 16 20 80 10 0 5 3 14 18 127 147 251 320 15 0 8 3 11 14 10 0 5 3 14 18 127 146 236 300 10 0 4 1 17 22 15 0 10 8 10 13 139 159 256 326 15 0 8 3 11 15 15 0 10 8...

Страница 20: ...0 5 2 8 10 110 10 0 5 0 11 14 91 105 408 520 15 0 10 5 6 7 10 0 5 0 11 15 97 111 410 522 10 0 5 2 8 10 15 0 10 2 7 9 91 105 403 513 15 0 10 5 6 7 15 0 10 2 8 10 97 111 404 515 75 10 0 4 7 13 16 70 10...

Страница 21: ...0 0 6 4 30 39 80 10 0 7 5 28 36 131 151 254 323 15 0 13 2 20 26 10 0 7 5 29 37 131 150 236 300 10 0 6 4 33 41 15 0 15 1 20 26 143 164 259 329 15 0 13 2 22 28 15 0 15 1 21 26 142 164 240 305 90 10 0 6...

Страница 22: ...7 7 18 23 110 10 0 6 1 21 27 90 104 420 534 15 0 15 6 13 16 10 0 6 1 22 28 96 110 421 536 10 0 7 7 18 23 15 0 12 5 14 18 90 104 406 517 15 0 15 6 13 16 15 0 12 5 15 19 95 110 407 518 75 10 0 7 0 26 33...

Страница 23: ...293 10 0 4 6 61 77 80 40 0 4 7 13 17 127 146 252 321 15 0 9 4 41 52 40 0 4 7 13 17 126 146 235 299 10 0 4 6 65 82 60 0 9 5 9 12 137 158 256 326 15 0 9 3 43 55 60 0 9 5 10 12 136 157 238 302 90 10 0 4...

Страница 24: ...54 90 40 0 4 1 13 16 118 135 335 426 15 0 9 8 30 38 40 0 4 1 14 17 126 145 339 431 10 0 4 8 43 54 60 0 8 5 9 11 117 135 321 408 15 0 9 8 30 39 60 0 8 5 9 12 126 145 324 412 10 0 4 8 37 47 110 40 0 3 9...

Страница 25: ...y check out the system and units before and during start up This form need not be returned to the factory unless requested during technical service support MODE Heat Cool Source Load Source Load Enter...

Страница 26: ...ale This service should be performed by an experienced service person WARNING Hazardous Chemicals Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with ski...

Страница 27: ...conditioned space the unit may not start in cool weather approximately 45 F It may then be necessary to startthe unit in the cooling mode for three to five minutes The unit may then be shut off there...

Страница 28: ...M X Water too cold Increase temperature X X Undercharged with refrigerant Increase charge X X Defective pressure switch Replace X X Heat transfer fluid too cold Raise water temperature Freezestat open...

Страница 29: ...WSHP SVX02C EN 29 Wiring Figure 10 Deluxe 24V single circuit single phase...

Страница 30: ...Figure 11 Deluxe 24V dual circuit three phase Wiring 30 WSHP SVX02C EN...

Страница 31: ...startup not to exceed 18 months from shipment Extended Warranty The optional extended warranty is a second through fifth yearwarranty The time startsatthe endofstandard1 year coverage through the fift...

Страница 32: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: