Refrigerant Line
Table 12.
Refrigerant Line Connection Sizes
Model
Vapor Line Connection
Liquid Line Connection
TAMXB0A24V21DA
3/4
3/8
TAMXB0B30V31DA
3/4
3/8
TAMXB0C36V31DA
7/8
3/8
TAMXB0C42V41DA
7/8
3/8
TAMXB0C48V41DA
7/8
3/8
TAMXB0C60V51DA
7/8
3/8
Notes:
1.
This table indicates the tubing connection diameters at the indoor coil. A field supplied reducing coupling may be required.
2.
All AHRI listed systems are tested with 25 feet of refrigeration tubing; the rated tubing diameters are located in the electronic performance
data system.
3.
If the refrigeration lines exceed 60 feet in linear length and/or if alternate size refrigeration tubing is present at the job, please consult SS-
APG006–EN or 32–3312** (latest version)
Refrigerant System Layout
Vapor Line
Liquid Line
Strainer
Evaporator Temperature
Sensor (ET)
- Located on 3/8” aluminum
distributor tube
(orange wires)
EEV Stepper
Motor
Saturation Temperature Sensor
(SAT Yellow Wires)
Gas Temperature Sensor (GT)
- Located on copper section of manifold
(Black or Brown wires)