background image

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service informa-
tion pack upon completion of work.

 

HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

WARNING:

Installer’s Guide

A. GENERAL INFORMATION

WARNING

!

THIS INFORMATION IS FOR USE BY INDIVIDUALS HAVING
ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANI-
CAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL
AIR CONDITIONING PRODUCT MAY RESULT IN PER-
SONAL INJURY AND/OR PROPERTY DAMAGE. THE MANU-
FACTURER OR SELLER CANNOT BE RESPONSIBLE FOR
THE INTERPRETATION OF THIS INFORMATION, NOR CAN
IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.

CAUTION

!

To prevent shortening its service life, the air handler should

not be used during the finishing phases of construction.  The
low return air temperatures can lead to the formation of con-
densate.  Condensate in the presence of chlorides and fluo-
rides from paint, varnish, stains, adhesives, cleaning com-
pounds, and cement creates a corrosive condition which may
cause rapid deterioration of the cabinet and internal compo-

nents.

These instructions do not cover all variations in systems or
provide for every possible contingency. Should further in-
formation be desired or particular problems arise which
are not covered sufficiently by this manual, contact your
local distributor or the manufacturer as listed on the air
handler nameplate.

These Air Handlers are shipped from the factory in the
upflow or horizontal right configuration and are fully con-
vertible to downflow or horizontal left. Refer to Section B
beginning  on page 3  for additional information.

INSPECTION

Check carefully for any shipping damage. This must be re-
ported to and claims made against the transportation com-
pany immediately. Check to be sure all major components
are in the unit. Any missing parts should be reported to
your supplier at once, and replaced with authorized parts
only.

Convertible Variable Speed –
Air Handlers  2 1/2 - 5 Ton

TWE031E13FB; TWE037E13FB;
TWE040E13FB; TWE049E13FB;
TWE065E13FB

Contents

General Information .............................................. 1

Installation Limitations & Recommendations ............................ 1

Unit Installation ...................................................... 3

Vertical Upflow ......................................................................... 3
Vertical Downflow .................................................................... 3
Horizontal Left .......................................................................... 4
Horizontal Right ....................................................................... 4

Refrigerant Piping ................................................. 5

Condensate Drain Piping ...................................... 6

Electrical - Wiring ................................................... 7

Airflow Adjustment ................................................. 9

Hook Up Diagrams ................................................. 8

Outline Drawings ................................................. 10

Checkout Procedures .......................................... 12

INSTALLATION LIMITATIONS & RECOMMENDATIONS

The general location of the air handler is normally se-
lected by the architect, contractor and/or home owner for
the most effective application and satisfaction.

These air handlers are suitable for installation in a
closet, alcove or utility room with free, non-ducted, air
return, using the area space as a return air plenum.
With ducted supply air, if the minimum clearances to
combustible materials and service access are observed,
the above installations are suitable.

NOTE:  Condensation may occur on the

surface of the air handler when installed in
an unconditioned location.  When units
are installed in unconditioned spaces,
verify that all electrical and refrigerant line
penetrations on the air handler are sealed
completely.

 This area may also be used for other purposes, includ-
ing an electric hot water heater - but in no case shall

18-GE01D1-9

Содержание TWE031E13FB1

Страница 1: ...on and are fully con vertible to downflow or horizontal left Refer to Section B beginning on page 3 for additional information INSPECTION Check carefully for any shipping damage This must be re ported...

Страница 2: ...r or by oth ers then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing a fossil fuel device be installed and...

Страница 3: ...ee Figure 3 c Position unit on Pedestal or other suitable foun dation If Pedestal is not used a frame strong enough to support the total weight must be pro vided Provide a minimum height of 14 inches...

Страница 4: ...shown in the outline drawing HORIZONTAL LEFT a For maximum efficiency and Customer ease of filter maintenance it is recommended that a prop erly sized remote filter and grille be installed for horizo...

Страница 5: ...ush fit for 3 4 or 1 1 2 duct board applications see the Outline drawing on page 10 for sizes of the duct connections After the duct is secured seal around the supply duct to prevent air leakage NOTE...

Страница 6: ...imary drain See Figure 6 Two secondary drain connections are provided for the different orientations See Figure 6 The lower of the two should be connected as a backup to prevent conden sate overflow b...

Страница 7: ...SWITCHES AS SHIPPED COOLING HEATING AIRFLOW FAN OFF DELAY AUXILIARY HEAT SPEEDS 0 OFF OFF 50 80 100 if necessary 50 Dehumidify Fast Coil Cooling and Heating Efficiency 7 5 minutes 3 minutes 1 minute...

Страница 8: ...8 18 GE01D1 9 Installer s Guide TWE E AIR HANDLERS WITH SINGLE STAGE COOLING 2 STAGE HEAT TWE E AIR HANDLERS WITH TWO STAGE COOLING 2 STAGE HEAT From Dwg No B801074...

Страница 9: ...the unit 3 Field wiring diagrams are provided which show the low voltage wiring hookup for a single speed cooling only system with supplementary heaters and a heat pump system with supplementary heat...

Страница 10: ...STIBLE MATERIAL REQUIRED SERVICE CLEARANCE RECOMMENDED SIDES 0 2 FRONT 0 21 BACK 0 0 INLET DUCT 0 1 OUTLET DUCT 1 1 FOR THE FIRST 3 FT OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALLED EXCEPT MODELS...

Страница 11: ...0 21 00 1 50 CAGE NUT MOUNTING LOCATION FOR TWE AIR HANDLERS FOR TWO PIECE CABINET ONLY Model No H W A B TWE031E13 43 00 21 50 17 00 39 00 TWE037E13 45 00 23 50 19 00 41 00 TWE040E13 51 75 26 00 23 80...

Страница 12: ...e that grounding of unit is in accord with code 3 Make sure unit suspension if used is secure and that there are no tools or loose debris in around or on top of the unit 4 Check all duct outlets they...

Отзывы: