Modules are addressed from 1 and upwards. Do not use position 0.
Address setting of modules:
Address
MSB
LSB
Comments / labelling
0
0
Do not use
1
0
1
M2
2
0
2
M3
3
0
3
M4
4
0
4
M5
5
0
5
M6
6
0
6
M7
7
0
7
M8
8
1
0
M9
9
1
1
M10
10
1
2
M11
11
1
3
M12
12
1
4
M13
13
1
5
M14
14
1
6
M15
15
1
7
M16
16
2
0
M17
17
2
1
M18
18
2
2
M19
19
2
3
M20
20
2
4
M21
21
2
5
M22
22
2
6
M23
23
2
7
M24
24
3
0
M25
25
3
1
M26
26
3
2
M27
27
3
3
M28
28
3
4
M29
29
3
5
M30
30
3
6
M31
31
3
7
M32
RS-485 circuitry
The communication circuitry has a built-in snubber circuit which eliminates the need of
end resistor. The transceiver circuit is s hort circuit safe and is over voltage protected.
Network cables
Minimum requirements for communication cables: Characteristic impedance 1 00-250
Ohm, 2x twisted pair and outer screen. Cable terminated in a RJ -
45 plug. Signal ‘A’ –
Pin 3, signal ‘B’ – Pin 6, signal ‘Ref’ – Pin 4 and 5.
LEDs
There are four LEDs on each output module: Power indicate s that logic power supply
(24VDC) is present to the module, Rx indicates messages received to the module, T x