Model

SWSeries II

Nominal DC Input Voltage

12 VDC

12 VDC

24 VDC

24 VDC

48 VDC

48 VDC

48 VDC

48 VDC 

AC Output Voltage (RMS)

120 VAC

230 VAC

120 VAC

230 VAC

120 VAC

230 VAC

120 VAC

230 VAC

Nominal Frequency

60 Hz

50 Hz

60 Hz

50 Hz

60 Hz

50 Hz

60 Hz

50 Hz

Continuous Power @ 20°

2500 VA

2600 VA

4000 VA

3300 VA

4000 VA

3300 VA

5500 VA

4500 VA

Continuous AC Output (@ 25°C)

21 amps

11 amps

33 amps

14 amps

33 amps

14 amps

46 amps

20 amps

Maximum AC Output (RMS)

60 amps

28 amps

78 amps

34 amps

78 amps

34 amps

78 amps

34 amps

Efficiency (peak)

90%

90%

94%

94%

95%

95%

96%

96%

Automatic AC Transfer Relay

60 amps

30 amps

60 amps

30 amps

60 amps

30 amps

60 amps

30 amps

Maximum Charging Rate

150 amps

150 amps

120 amps

100 amps

60 amps

50 amps

75 amps

60 amps

DC Input Requirements

Search Mode

0.08A (1W)

0.08A (1W)

0.04A (1W)

0.04A (1W)

0.025A(1W)

0.025A(1W)

0.04A (1W)

0.04A (1W)

On Mode (no load - idle)

1.0A (12W)

1.6A (12W)

0.66A (16W)

0.66A (16W)

0.33A (16W)

0.33A (16W)

0.40A (20W)

0.40A (20W)

At Full Rated Power

275 amps

150amps

200 amps

166 amps

100 amps

83 amps

137 amps

106 amps

Short Circuited Output

700 amps

300 amps

360 amps

320 amps

180 amps

160 amps

180 amps

138 amps

Nominal DC Input Voltage Range

11.8 to 16.5

11.8 to 16.5

22 to 33

22 to 33

44 to 66

44 to 66

44 to 66

44 to 66

AC Output Characteristics

AC Output Waveform

Sinewave, 34 to 52 steps per cycle

Voltage Regulation

+/- 2%

Total Harmonic Distortion

3 to 5% (stand alone operation)

Power Factor Allowed

-1 to 1

Frequency Regulation

+/- 0.04% (crystal regulated)

Load Sensing Range

16 to 240 Watts

Options

Remote Control Panel (50 ft. max.)

SWRC

SWRC

SWRC

SWRC

SWRC

SWRC

SWRC

SWRC

Stacking Interface for double power

SWI*

No

SWI*

No

SWI*

No

SWI*

No

(*requires two inverters)

(120/240)

(120/240)

(120/240)

(120/240)

Conduit Box

SWCB

SWCB

SWCB

SWCB

SWCB

SWCB

SWCB

SWCB

DC Disconnect Breaker

DC 250

DC 250

DC 250

DC 250

DC 175

DC 175

DC 250

DC 175

DC Battery / Inverter Cables

BC5-4/0

BC5-4/0

BC5-4/0

BC5-4/0

BC5-2/0

BC5-2/0

BC5-4/0

BC5-2/0

Enclosure Type

Indoor, ventilated, steel chassis with powdercoat finish

Specified Temp Range

32° F to 104° F (0° C to +40° C) (output will meet specified tolerances)

Allowed Temp Range

-40° F to 140° F (-40° C to +60° C) (output may not meet specified tolerances)

Dimensions - Inverter Only

15" (38 cm) high, 22.5" (57 cm) wide, 9" (23 cm) deep (when wall mounted)

Dimensions - Shipping

20.5" (52 cm), 27" (69 cm), 15.5" (40 cm)

Mounting

Wall or Shelf Mount

Weight - Inverter Only

90lbs (42kg)

95lbs (43kg)

105lbs (48kg) 105lbs (48kg)

105lbs (48kg)

105lbs (48kg)

136lbs (63kg)

136lbs (63kg)

Weight - Shipping

96lbs (44kg)

110lbs (50kg)

111lbs (50kg) 111lbs (50kg)

111lbs (50kg)

111lbs (50kg)

143lbs (65kg)

143lbs (65kg)

S P E C I F I C A T I O N S

ENGINEERING

THE POWER COMPANY

Available From:

Utility Interactive Mode:

Operating as a bi-directional battery charger, power from any source that tries to

raise the batteries above their programmed float voltage is delivered to the grid. A GRID USAGE TIMER can be
set to allow selling of electricity to the utility only during prescribed hours. Sell back current is adjustable.
Caution: Utility intertie must have approval of local utility company.

Peak Load Shaving Modes

- (1) The sine wave series may be programmed to operate from batteries during a

specified period of the day. Batteries may be charged during lower rate periods. (2) During a programmable
time of the day, power is delivered to the grid from the batteries. An alternative (lower) adjustable float voltage
is employed to allow variable battery discharge depths.

Three user adjustable voltage-controlled signal relays are provided to control charging sources and loads.

Selecting modes, enabling features and adjusting parameters are easily accomplished by moving thru a menu tree
that is displayed on the control panel’s LCD read-out. Doubling as a meter, the LCD displays INVERTER AMPS,
INPUT AMPS, LOAD AMPS, BATTERY VOLTS DC and INVERTER VOLTS AC. Additionally, control panel LED’s report
the status of eight system conditions.

Specifications

SW2512

SW2612E

SW4024

SW3024E

SW4048

SW3048E

SW5548

SW4548E

*specifications may change without notice

Options:

Remote control panel (SWRC), stacking interface cable (SWI), conduit box for code approved DC input battery cables (SWCB).

Other Voltage/frequency for export are as follows: 

SW3024J=105VAC/50Hz

SW4024K=105VAC/60Hz

SW4024W=220VAC/60Hz (two wire output only)

SW4548A-240VAC/50Hz

®

LISTED

C

67664

®

LISTED

67664

POWER CONDITIONING UNITS FOR 
USE IN PHOTOVOLTAIC POWER 
SYSTEMS             STANDARD UL1741

POWER CONVERTERS AND POWER
CONVERTER SYSTEMS FOR
RECREATIONAL VEHICLES
STANDARD   UL458

COMMERCIAL AND INDUSTRIAL 
POWER SUPPLIES
CERTIFIED TO
CAN/CSA-C22.2 NO. 107.1-M1

ETL TESTING LABS. INC
CORTLAND, N.Y.

Rev# 11/97

5916  195th St. N.E.  ARLINGTON, WA. USA 98223  Phone (360) 435-8826  Fax (360) 435-2229  Web: www.traceengineering.com 

5400

5200

5000

4800

4600

4400

4200

4000

3800

3600

3400

3200

3000

2800

2600

2400

2200

2000

1800

1600

1400

1200

1000

800

600

400

200

0

120%

100%

80%

60%

40%

20%

0%

SW5548

SW458E

SW2612E

SW2512

SW4024 / SW4048

SW3024E / SW3048E

AC Load Watts

Efficiency

SW Series Efficiency Curves