Installation manual 

 Mamba II

Resistance to strong winds can be observed in the test mode in windy weather. The signal level indicator should
remain spontaneously in the wind at more than 3 pieces of signal. You can check in the windy weather also the
stability of the tension mesh fence and stability of all parts of the fence. Remove the mechanical deformation of
the cable.

3.5. FIRST START 

Switch ON the sensor 

When the power supply is connected 

 first is green LED light, then blink yellow and finally red LED.

Now is a slight delay (about 1 second) tested the integrity of the sensor and cable.

If the cable is connected, integrity of the cable is OK and is properly terminated, after a while, the yellow LED goes
out.

If the sensor is working properly, the red LED will also be illuminated for approximately one second.

Now is system ready for use.

The described behaviour is valid if the sensor in the factory setting. The control software can change the
configuration of fault LEDs. Setting fault diodes is derived from the software settings.

The described behaviour is valid if the sensor in the default factory setting. The control software can change the 
configuration of trouble LEDs. Software settings can change status of trouble diodes.  

Содержание Mamba II

Страница 1: ...Version 2013 2 Installation manual Mamba II...

Страница 2: ...ons and tips for assembly 5 3 Installation 6 3 1 Instalation of the device 6 Important notice 6 3 2 Cabeling 8 Preparation of RG59 cable 9 Preparation of senstive cable 9 Cable connection 9 Cable term...

Страница 3: ...immediately generates an alarm signal The sensor is typically mounted directly to the fence or fence posts see Chapter 1 4 Installation requirements and procedures Sensing cable is securely fastened t...

Страница 4: ...su cient cable tension and uniform strength of tightening strips It is advantageous to use a special mounting strips tongs If the cable is routed through a column or other reinforcement set higher ten...

Страница 5: ...metal fence Wooden fence Barber fence There is possibility to use standard mounting method in most cases for the wired fences If you would like to install system to the concrete or other solid fence...

Страница 6: ...m diameter of 1 mm see Fig 5 Minus pol of power supply IS NOT grounding of the sensor Before connecting the sensor to the installed cable be sure that the impedance between the cable shield and wires...

Страница 7: ...y 1 32 see Section 3 3 Controls Rotary switch 0 9 Sensitivity 0 lower 9 higher Terminals IN Connection of sensitive detection cable Terminal IN wires and GNDA shield GNDA NC1 Output ALARM normally clo...

Страница 8: ...VIBRO cable Connection of the cable and the sensor Use the special joints for connecting cables and sensor MAMBA There are two types of cable connectors The first is for transform sensitive cable to...

Страница 9: ...ATION OF SENSTIVE CABLE Preparation of sensoric cable describe following Fig 11 unscrew the end of the joint put the rubber seal to the cable from the cable gland remove the isolation from 35 to 40 mm...

Страница 10: ...ity This sensitivity is used mainly for solid fences Switch no 2 see Chapter 3 4 Testing mode Switch no 3 switching ON OFF reed relay on mainboard which is connected in serial with output NC2 Connecti...

Страница 11: ...een Not used in test mode When adjusting the sensitivity proceed as follows Switch ON Test mode Turn off extra sensitive mode DIP switch no 1 Set the rotary switch to the middle sensitivity Check the...

Страница 12: ...a slight delay about 1 second tested the integrity of the sensor and cable If the cable is connected integrity of the cable is OK and is properly terminated after a while the yellow LED goes out If th...

Страница 13: ...f the software Setting the address of the sensor is described in chapter 3 3 Controls Speed of communication BUS is in default set to 19 200 Baud do not change this setting Is necessary to set right a...

Страница 14: ...this section you can set the sensor detection algorithm for the particular type of installation WIRED FENCE this setting is right for most types of the flexible fences SOLID FENCE Sensitive algorithm...

Страница 15: ...ES AND CONDITIONS writing to memory start automatically after selecting value in the menu You can adjust reducing of sensitivity in the pop up menu digital input Activation is performed by connection...

Страница 16: ...h on the mainboard of the sensor When you connect the sensor software automatically retrieves the current sensitivity setting from EPROM Writing new settings to memory start automatically after select...

Страница 17: ...er voltage level is lower than value set in the pop up menu 5 Shaking activation of tilt detector 6 End terminal error of termination terminator on the cable is not connected or integrity of the cable...

Страница 18: ...of small signal levels The horizontal dashed lines shows the alarm level If the signal exceeds a preset threshold detection algorithm evaluates alarm values red curve shows the alarm status This cond...

Страница 19: ...the values from the sensor Software show signal waveforms on a graph and display current values on tab detail If you want to make forensic analysis of the recorded values stop reading 2 Save Load dat...

Страница 20: ...lly inserted Check all cable joints Check all cable connections The yellow LED T1 illuminates Cover of the sensor is open tamper ALLWAYS Reed Relay on the main board has not on the other side magnet a...

Отзывы: