Parameterization and configuration
TR-Electronic GmbH 2009, All Rights Reserved
Printed in the Federal Republic of Germany
Page 80 of 92
TR - ELA - BA - DGB - 0015 - 13
04/23/2020
Operating parameter Option 1
Description see page 83
unsigned16
Byte
X+10
X+11
Bit
15
– 8
7
– 0
Data
2
15
– 2
8
2
7
– 2
0
Default (dec.)
0: In case of a measurement error only
the
Data status
is active (0…1)
Option 1
6.4 Description of the operating parameters
6.4.1 Interpolation
This function is not supported at Soft. No 5641 !
Selection
Description
Default
off
A new position value is output according to the
internal measuring system cycle time. If the bus
cycle time corresponds to the internal measuring
system cycle time, in this case a new position value
will be output each bus cycle.
X
on
If the internal measuring system cycle time is much
greater than the bus cycle time, it may be useful to
switch on the interpolation.
Recommendation:
In case of bus cycle times ≤ 4 ms
--> switch on Interpolation
Intermediate position values can then be calculated
through internal measured value processing. These
calculated position values have a much smaller cycle
time than the internal measuring system cycle time.