3.4 Terminal Connections
3.4.1 Power Connections
All power connections are on the main terminal block (H1), which has 18
terminals.
Note: The power connections detailed below are for normal mains
power. Refer to section 10.3 for power wiring details when the 12V
DC power option is fitted.
Terminal
No.
Connection
Colour
1
220 / 240V AC Active input
Brown (standard colour)
2
Duplicate 240V AC Active contact.
Brown (standard colour)
3
Duplicate 240V AC Active contact.
Brown (standard colour)
4
220 / 240V AC Earth input
Green (standard colour)
5
Duplicate 240V AC Earth contact.
Green (standard colour)
6
Duplicate 240V AC Earth contact.
Green (standard colour)
7
220 / 240V AC Neutral input
Blue (standard colour)
8
Duplicate 240V AC Neutral
contact.
Blue (standard colour)
9
Duplicate 240V AC Neutral
contact.
Blue (standard colour)
10
Normally Closed contact of Lower
relay output
Customer Defined
11
Common contact of Lower relay
output
Customer Defined
12
Normally Open contact of Lower
relay output
Customer Defined
13
Normally Closed contact of Upper
relay output
Customer Defined
14
Common contact of Upper relay
output
Customer Defined
15
Normally Open contact of Upper
relay output
Customer Defined
16
No Connection
17
+ve of current or voltage output
Customer Defined