6
Multi
Average Traverse
1.
Turn the SP555 on and connect it to the TPI View App.
2.
Select
Multi
Average in the TPI View App. Determine the type and size of the
duct (grill) and enter it into the View App.
3.
Position the SP555 at one end of the grill. The arrow on top of the SP555
indicates the direction it should be oriented in the air flow.
4.
Tap "Start Test" to begin the traverse test.
5.
Move the SP555 along the grill from one end to the other
stopping at test
points
.
Once stopped tap "Add to Average" to add the reading to the overall
average readings.
NOTE: Stop every inch or so. The more readings you add
to the average the more accurate the average will be.
Once you reach the
end tap "Stop Test". (See Picture Below)
6.
The average air velocity, air flow (CFM), and temperature will be displayed.
7.
A report can be created and data can be saved to a job by tapping on
"Create Report".
Stop at each test point and tap "Add To
Average". The more test points added
the more accurate the average will be.