12
JetStream Gigabit Smart Switch
Cable
Pave Way
Min Parallel
Length (mm)
2~5kVA
powerline
Parallel cabling
300
One is in the grounded metal raceway or metal pipe
150
The both are in the grounded metal raceway or metal
pipe
80
>5kVA
powerline
Parallel cabling
600
One is in the grounded metal raceway or metal pipe
300
The both are in the grounded metal raceway or metal
pipe
150
Device
Min Distance (m)
Switch case
1.00
Transformer room
2.00
Elevator tower
2.00
Air-conditioner room
2.00
3.2 Connect to Ground
Connecting the device to ground is to quickly release the lightning over-voltage and
over-current of the device, which is also a necessary measure to protect the body from
electric shock.
In different environments, the device may be grounded differently. The following
will instruct you to connect the device to the ground in two ways, connecting to the
grounding bar or connecting to the ground via the power cord. Please connect the
device to ground in the optimum way according to your specific operation environment.
■
Connecting to the Grounding Bar
If the device is installed in the Equipment Room, where a grounding bar is available,
you are recommended to connect the device to the grounding bar as shown in the
following figure.
Switch (Rear Panel)
Ground Cable
Grounding Terminal
Grounding Bar
Figure 3-1 Connecting to the Grounding Bar
Lightning Protection
Содержание JetStream T1600G-28TS
Страница 27: ......
Страница 28: ...Website http www tp link com E mail support tp link com 7106505040 REV1 0 0...