– 9 –
• Fan speed control when “Auto” is selected in fan mode
When “Auto” is selected,the fan speed is automatically controlled according to the difference between the room
and designated temperatures.
ROOM TEMP.
DESIGNATED TEMP.
Hi
Me
Lo
Hi
INDOOR FAN
+
3
℃
+
1
℃
+
3.7
℃
+
1.7
℃
+
0.7
℃
Me
• Method of anti-freezing control of heat-exchanger(indoor)
When the sensor(heat-exchanger) detects the temperature below 2
°
C for the duration of one minute,the
compressor stops the operation.
※
When indoor units in Room A1, A2 are operating simultaneously, even if only the sensor(heat-excanger) of
the indoor unit in Room A1(or Room A2) detects the temperature below 2
°
C, the compressor dose not stop.
The expansion valve of A1(or A2) cycle is closed completely to stop refrigerant flow.
After that, the compressor will automatically resume the operation
when the sensor(heat-exchanger) detects the temperature 2
°
C and above.
TEMPERATURE,
INDOOR HEAT
EXCHANGER
ON
ON
ON
OFF
COMPRESSOR
2
℃
OFF
3min
1min
OPERATION DETAILS