First, distinguish a location of malfunction.

(1) Is it a malfunction of a controlled part?

(2) Is it a malfunction of a controlling part?

(1) includes actual waking parts of 

refrigeration cycle and motors.

(2) includes circuit board.

First thing to do is to check the circuit board.

Is the circuit board trying to run?

Ex: Fan does not turn. 

®

 It cannot be distinguished if it is a 

malfunction of the fan, or of the circuit board. 

®

 Turn the air 

blower on. 

®

 Is there voltage at the fan motor terminal of the 

circuit board? 

®

 If so, the circuit board is normal. If not, the 

circuit board is malfunctioning.

This is how to distinguish between:

(1) Is it a malfunction of a controlled part?

(2) Is it a malfunction of a controlling part?

Problems of a circuit board can be roughly divided into two groups.

1. Malfunction of microcomputer-controlled parts such as relays.

2. Malfunction of microcomputer

In either case, replace the circuit board.

For the problems such as dirt on a cooling unit, it is important to 
perform a visual check first.

Part replacement is not necessary, and accurate analysis cannot 
be performed with an unclean condition.

Check the refrigeration cycle, It is easier by comparing 
temperatures at the evaporator inlet and outlet ports.

Problems that can be usually checked in the market place are:

• Coolant shortage

• Blockage of capillaries

In most cases, temperature of evaporator outlet port becomes high.

There is a possibility that problems are 
caused by part malfunctions. It is 
necessary to check parts of each part.

In the case of (1), distinguish further:

(3) Is it a problem of refrigeration cycle?

(4) Is it a problem of auxiliary devices?

(3) includes problems related to 

refrigeration cycle such as capillary 
blockage, coolant shortage and dirt on 
a cooling unit.

(4) includes problems related to a fan 

motor, compressor, louver motor, and 
thermistor.

For problems of auxiliary devices, check 
visually and/or by monitoring the status of 
the devices.
• Motor is not rotating.
• Compressor is not running.
• Louver motor does not run.

TROUBLESHOOTING OUTLINE

  TAD-T32G  (Service  Manual)    07.1.17  3:03  PM    ページ 10

Содержание TAD-T32G

Страница 1: ...SERVICE MANUAL MODEL TAD T32G Type A B TAD T32G Service Manual 07 1 17 3 03 PM b...

Страница 2: ...if the unit is to be used exclusively in one space the cooling efficiency will be enhanced by using the venting kit accessory which is included with the unit 2 OPERATIONAL FEATURES 1 COOLING OPERATION...

Страница 3: ...ertical louver Emergency ON OFF switch Front panel Air outlet grille Air intake grille HAF filter inside Charcoal filter inside Filter clamp inside Air intake opening Drain water outlet LCDI Power plu...

Страница 4: ...r Clock indicator Timer setting indicator Timer ON OFF indicator C F indicator Set temp indicator Mode indicator Fan speed indicator Symbols Cooling mode High speed Dehumidify mode Fan only mode Auto...

Страница 5: ...power cord in any way DO NOT apply any excessive force or pressure to the power supply cord Make sure that the plug is free of dust DO NOT use an extension cord DO NOT turn on and off by inserting or...

Страница 6: ...R OPERATING CYCLE MODEL OUTPUT POWER UNIT in FT2 V Hz V B T U GAL H A W CFM W uF V A W uF V W uF V W mm R22 lbs F lbs TAD T32G 20 W 16 1 2 D 36 H 508 W 418 D 915 H mm 194 258 18 24m2 115 60 104 127 12...

Страница 7: ...e The setting range is from 64 F 18 C to 90 F 32 C Note When choose AUTO DEHUMIDIFY or FAN MODE temperature setting button invalid Clock Set Controls Press CLOCK button LCD clock display flashes Press...

Страница 8: ...pleted after one beep Default indicator Trouble shooting when environmental tempera ture indicator failures Please check the environmental temperature indi cator on PCB if it s assembled properly and...

Страница 9: ...crews from the top of the rear panel I to remove the front cover Lift up the front cover and disconnect the connecters of the circuit board and the ionizer Type A only 2 Remove six 6 screws from the b...

Страница 10: ...a power failure The plug is not connected The timer is unable to work The main switch has not been pressed The set temperature is too close to the room s temperature There is something blocking the s...

Страница 11: ...as dirt on a cooling unit it is important to perform a visual check first Part replacement is not necessary and accurate analysis cannot be performed with an unclean condition Check the refrigeration...

Страница 12: ...sconnect the wiring of the load that is not moving from the main board apply voltage directly to the load to checkif the load is normal If the load is normal the problem is the main board Minimum set...

Страница 13: ...voltage It is not rotating It is rotating Normal Measure terminal voltage of main board Check drain motor rotation Drain motor malfunction Main board malfunction Operation stops due to full water TRO...

Страница 14: ...l if it is operated Check if there is loose disconnection short circuiting on connector of Full Tank Switch Also check a loose disconnection and breakage of Float Malfunction of Drain Motor Replace it...

Страница 15: ...again after 5 min of disconnection from power supply Normal if the unit is operated for 30 min after disconnection from power supply Operation Circuit Board is malfunctioned if the same problem happe...

Страница 16: ...room temperature drops more than 2 F 1 C from the setting temperature the compressor stops D When the room temperature is 2 F 1 C lower than the setting temperature the compressor will not start E The...

Страница 17: ...F 68 F 22 C 20 C C Less than 66 F 19 C Compressor ON 9min 3min 9min 3min 6min 3min Selected fan speed Low Low Low IONIZER INDOOR MOTOR SENSOR CN 3 CN 4 CN 5 P8 P1 R S T P2 P3 P4 P7 P6 P5 COM NO CN 2...

Страница 18: ...fan Capacitor A Rear FM Front fan motor Front fan Capacitor B Compressor Main circuit board Capacitor C Front FM Indication lamp circuit Front panel Power supply cord Rear panel Intake air grille HAF...

Страница 19: ...TOYOTOMI CO LTD 5 17 Momozono cho Mizuho ku Nagoya 467 0855 Japan www toyotomi jp New 12 06 Printed in Japan TAD T32G Service Manual 07 1 17 3 03 PM a...

Отзывы: