INSTALLATION OF HEATER AND FLUE PIPE
IMPORTANT:
Check and comply with all state and local codes that may apply to vented heaters before
beginning installation.
NOTE:
This heater is designed to be used at altitudes up to 3,000 FT. above sea level.
For use at altitudes higher than 3,000 FT. and up to 6,000 FT., adjustments to the heater must be
made. Consult with your dealer.
1.
Select heater location. Allow clearances as indicated below between heater and all other materials.
(See Fig. 1)
* Zero clearance is allowed between rear guards and all other materials to the rear of the heater.
2.
Make sure that the outside area to where the standard flue pipe will reach is clear of any objects.
(See Fig. 2 & 3)
CAUTION! The standard flue pipe installation, as shown in Fig. 2, is for wall thickness from 4 in. to 9 in.
ONLY.
Note: For wall thickness more than 9 in., refer to page 18 for available flue pipe extensions.
Note: The flue pipe can be installed through any standard building materials.
22
More than 1 ft.
More than 1 ft.
More than 5 ft.
More than 2 ft.
More than 4 inches
Fig. 1
Not less than 2 ft.
Combustible object
NonCombustible
object
Not less
than 1 ft.
Not less
than 1.5 ft.
Not less
than 1.5 ft.
*Not less
than 8 in.
Not less
than 2 ft.
Combustible object
45˚
Flue pipe
* Be sure this
clearance will
be maintained
after snowfalls,
etc.
Fig. 2
Fig. 3
<Standard Flue Pipe Installation>