76
GB
North America
Appliance Amps
(A)
AWG
10
18
13
16
18
14
25
12
30
10
40
8
Other Regions
Rated Current of
Appliance (A)
Nominal Cross-
Section Area
(mm
2
)
>3 and
≤
6
0,75
>6 and
≤
10
1
>10 and
≤
16
1,5
>16 and
≤
25
2,5
>25 and
≤
32
4
>32 and
≤
40
6
REQUIREMENTS OF THE MOUNTING STRUCTURE
§
The mounting rack must meet the relevant national or industrial standards
in terms of strength with welding and connection areas rustproofed.
§
The mounting rack and its load carry surface shall be able to withstand 4
times or above the weight of the unit, or 200kg, whichever is heavier.
§
The mounting rack of the outdoor unit shall be fastened with expansion
bolt.
§
Ensure the secure installation regardless of what type of wall on which it is
installed, to prevent potential dropping that could hurt people.
ELECTRICAL SAFETY REQUIREMENTS
§
Be sure to use the rated voltage and air conditioners dedicated circuit for
the power supply, and the power cord diameter must meet the national
requirements.
§
When the maximum current of air conditioner is
≥
16A, it must use the air
switch or leakage protection switch equipped with protection devices.
§
The operating range is 90% - 110% of the local rated voltage.But
insuf
fi
cient power supply mulfunction,electrical shock,or
fi
re. If the voltage
instability,proposed to increase the voltage regulator.
§
The minimum clearance between the air conditioner and the combustibles
is 1.5 m.
§
The interconnection cord connect the indoor and outdoor units. You must
fi
rst choose the right cable size before preparing it for connection.
§
Cable Types:
Outdoor Power Cable: HO7RN-F or HO5RN-F
Interconnection cord: HO7RN-F or HO5RN-F
§
Minimum Cross-Sectional Area of Power cable and interconnection cord: