11
7. Installation details
7.1 Wrench torque sheet for installation
Outside diameter
Torque
mm
inch
Kg
f.
m
Ф6.35
1/4
1.8
Ф9.52
3/8
4.2
Ф12.7
1/2
5.5
7.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
9K
12K
mm
2
1.5
1.5
7.3 Pipe length and the elevation
Capacity
Btu/h
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
G
as
Liquid
9k
3/8’’ (Ф9.52)
1/4’’ (Ф6.35)
5
5
10
30
12k
1/2’’ (Ф12.7)
1/4’’ (Ф6.35)
5
5
10
30
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be installed per 5-7 meters.
7.4 Air purging of the piping and indoor unit
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect