22
When using the “Extension pipe (L)” extension kit, the distance
between the heater exhaust pipe connection and the flue pipe
connection must be at least 1620 mm but no more than 2050 mm.
(See Figure 1 above.)
“Note that Exhaust Extension Kits L, M and S are designed for
installation inside the heated room, and for exposed (surface)
mounting only”.
No.
Name of Part
Q’ty
1
2
3
4
5
6
7
Adjustable Exhaust Pipe
Max. 1000 mm ~ Min. 570 mm
Exhaust Extension Pipe
(long, 1000 mm)
Intake Pipe (2000 mm)
Insulating Cloth Cover
(1000 mm)
Pipe Holder
Pipe Support Hardware
L-Shaped Exhaust Joint
1
1
1
2
2
3
sets
1
NOTE: Use “L”-shaped Exhaust Joint if necessary.
INSTALLATION WITH EXTENSION PIPE KIT (L)
Adjustable
Exhaust Pipe
Insulation
Cloth Cover
Exhaust Extension
Pipe (long)
Pipe
Holder
Intake Hose
Pipe Support
Hardware
(# 17187098)
(# 17212685)
(# 17206004)
(# 17206027)
(# 17206089)
(# 17206091)
(# 17206025)
Pipe Support Hardware
Pipe Holder (2 pcs.)
Pipe Holder Support (1 pc.)
Screw
(1 pc.)
Wood Screw
(2 pcs.)
Nut (1 pc.)
7
5
6
85 mm
90 mm
1
2
3
4
Max. 1000 mm
Max. 2000 mm
Max. 1000 mm
Max. 1000 mm ~ Min. 570 mm
Flue pipe
connection
Intake
Hose
Heater
Exhaust
pipe
connection
Figure 1
1620 ~ 2050 mm
EXTENSION PIPE KITS:
L, M and S are designed to extend both Supply and Exhaust Pipes from the back of the
heater to the Flue Pipe which is the only approved method of transporting hot flue gasses through a wall. The
extension pipes must be installed “exposed surface mounted” within the heated room.
Extension Pipe Kit (L) PART #17206013
EXTENSION PIPE KIT