Electrical Control Function
108
Electrical Control System
All protections are active and the same as that in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time.
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 The sleep function is available in cooling, heating or auto mode.
1.3.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed. (For floor-standing, the indoor fan is
fixed at auto speed)
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode but doesn’t turns off
1.3.7.4 Timer setting is available
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting automatically after 3 minutes when power returns.
1.3.9 Drain pump control (For Cassette)
Adopt the water-level switch to control the action of drain pump.
Main action under different condition :( every 5 seconds the system will check the water level one time)
1. When the A/C operates with cooling (including auto cooling), dehumidifying, and forced cooling mode, the
pump will start running immediately and continuously, till stop cooling.
2. Once the water level increase and up to the control point, LED will alarm and the drain pump open and
continue checking the water level. If the water level fall down and LED disalarmed (drain pump delay close 1
minute) and operate with the last mode. Otherwise the entire system stop operating ( including the pump)
and LED remain alarming after 3 minutes,
Содержание CCT 140IUINV
Страница 3: ...General Information General Information 1 Part 1 General Information 1 Model Lists 2 2 Features 4 ...
Страница 12: ...Dimensions 12 Super Slim Cassette Type 2 Dimensions Model A H CCT140IUINV 287 317 CCT160IUINV 287 317 ...
Страница 13: ...Service Space Super Slim Cassette Type 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 14: ...Wiring Diagrams 14 Super Slim Cassette Type 4 Wiring Diagram CCT140 IUINV CCT160 IUINV ...
Страница 26: ...Wiring Diagrams Duct Type 27 4 Wiring Diagrams DCT140 IUINV DCT160 IUINV ...
Страница 32: ...Field Wiring Duct Type 33 10 Field Wiring ...
Страница 35: ...Service Space Ceiling Floor Type 37 3 Service Space ...
Страница 36: ...Wiring Diagrams 38 Ceiling Floor Type 4 Wiring Diagrams CFT140 IUINV CFT160 IUINV ...
Страница 41: ...Field Wiring Ceiling Floor Type 43 9 Field Wiring ...
Страница 45: ...Service Space GA Floor standing Type 47 3 Service Space ...
Страница 46: ...Wiring Diagrams 48 GA Floor standing Type 4 Wiring Diagrams FS140IUINV FS160IUINV ...
Страница 56: ...Wiring Diagrams 70 Outdoor Units OU 1403 IUINV OU 1603 IUINV ...
Страница 80: ...Troubleshooting Electrical Control System 121 2 4 2 3 Up down panel is not closed ...
Страница 87: ...Troubleshooting 128 Electrical Control System 2 4 3 7 E6 malfunction Only for 48K with 1 phase ...
Страница 88: ...Troubleshooting Electrical Control System 129 2 4 3 8 P0 malfunction ...
Страница 89: ...Troubleshooting 130 Electrical Control System 2 4 3 9 P1 malfunction ...
Страница 90: ...Troubleshooting Electrical Control System 131 2 4 3 10 P2 malfunction ...
Страница 91: ...Troubleshooting 132 Electrical Control System 2 4 3 11 P3 malfunction ...