Troubleshooting
Electrical Control System
119
2.4.4.5. E5 malfunction (For single phase units)
Voltage protection
Check the voltage of
outdoor unit power supply,
whether the voltage
between L(1) and N is about
220~240VAC
Check the power supply
Check whether the voltage
of IPM board P and N is
normal? DC277-356V for
18K/24K/30KBtu/h; DC277-
410V for 36K/48KBtu/h
Replace bridge rectifiers,
and then check whether the
system can run normally
Replace IPM board, and
then check whether the
system can run normally
Replace outdoor main board
Yes
No
No
No
No
Yes
Trouble is solved
Yes
Yes
E5 display
Replace the power board,
then check whether the
system can run normally
No
Yes
Содержание CCT 100HINVi
Страница 1: ...Service Manual MODEL CCT 50HINVi o CCT 70HINVi o CCT 100HINVi o...
Страница 7: ...Indoor Units 6 Indoor Units Part 2 Indoor Units Super Slim Cassette Type 7...
Страница 13: ...Dimensions 12 Indoor Units 2 Dimensions Model A H 18 205 235 24 205 235 36 245 275...
Страница 14: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 15: ...Wiring Diagrams 14 Indoor Units 4 Wiring Diagrams CCT 50HINVi CCT 70HINVi CCT 100HINVi...
Страница 20: ...Field Wiring Indoor Units 19 9 Field Wiring...
Страница 25: ...Wiring Diagrams Outdoor Units 57 4 Wiring Diagrams CCT 50HINVo CCT 70HINVo...
Страница 26: ...Wiring Diagrams 58 Outdoor Units CCT 100HINVo...
Страница 45: ...Troubleshooting 108 Electrical Control System 2 4 1 2 Outdoor unit malfunction...
Страница 50: ...Troubleshooting Electrical Control System 113 2 4 2 3 Up down panel is not closed...
Страница 52: ...Troubleshooting Electrical Control System 115 2 4 4 For the outdoor unit 2 4 4 1 E0 malfunction...
Страница 54: ...Troubleshooting Electrical Control System 117 2 4 4 3 E3 malfunction...
Страница 55: ...Troubleshooting 118 Electrical Control System 2 4 4 4 E4 malfunction...
Страница 58: ...Troubleshooting Electrical Control System 121 2 4 4 7 E6 malfunction Only for MOU 36HFN1 QRC4 MOU 36HFN1 QRC8...
Страница 60: ...Troubleshooting Electrical Control System 123 2 4 4 9 P1 malfunction For 36k models...
Страница 61: ...Troubleshooting 124 Electrical Control System 2 4 4 10 P2 malfunction For 36k models...
Страница 62: ...Troubleshooting Electrical Control System 125 2 4 4 11 P3 malfunction...