HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
8
23
Gen Under Volt
(30-620)V
184
When generator voltage has fallen below the set
value and the “Gen abnormal delay” has expired,
Gen Under Voltage is active. When set the value as
30V, the controller does not detect under voltage
signal.
24
Under Speed
(0-6000)r/min
1200
When engine speed has fallen below the set value
for 10s, Under Speed is active. It will initiate a shut-
down alarm signal.
25
Over Speed
(0-6000)r/min
1710
When engine speed has exceeded the set value for
2s, Over Speed is active. It will initiate a shutdown
alarm signal.
26
Under Freq
(0-75.0)Hz
40.0
When generator frequency has fallen below the set
value but Not equal to 0 for 10s, Under Frequency
is active. It will initiate a shutdown alarm signal.
27
Over Freq
(0-75.0)Hz
57.0
When generator frequency has exceeded the set
value for 2s, Over Frequency is active. It will initia-
te a shutdown alarm signal.
28
High Temp.
(80-140)ºC
98
When the temperature value of the external
temperature sensor exceeds the set value, “High
Temperature” timer is initiated. Detecting only after
safety on delay has expired. If the set value is 140,
high temperature signal will not be sent (this only
concerns external temperature sensor, not high
temperature signal via config. input port).
29
Low OP
(0-400)kPa
103
When the external pressure sensor value falls
below this set value, “Low Oil Pressure” timer is
initiated. Detecting only after safety on delay has
expired. If the set value is 0, low oil pressure signal
will not be sent (this only concerns pressure sen-
sor and does not concern low oil pressure warning
signal via configurable input port)
30
Low Fuel Level
(0-100)%
10
When the liquid level of the external sensor falls
below the set value, “Low Fuel Level” timer is
initiated. (this only concerns fuel level sensor and
does not concern low fuel level warning signal via
configurable input port)
31
Aux. Sensor
(80-140)ºC (0-400)kPa
(0-100)%
98
Each value correspond to above 28 (Temperature
sensor), 29 (Oil pressure sensor) and 30 (Level
sensor), respectively.
32
Loss of Speed Signal (0-20.0)s
5.0
If the set value is 0, only warning and not to shut-
down the generator.
33
Charge Alt Failure
(0-30)V
6.0
During generator is normal running, when alterna-
tor D+(WL) voltage has fallen below the set value
and remains for 5s, It will initiate a shutdown alarm
signal.
34
Battery Over Volt
(12-40)V
33.0
When battery voltage has exceeds the set value
and remains for 20s, It will initiate a warning alarm
signal. Only warning and not to shutdown the
generator.
35
Battery Under Volt
(4-30)V
8.0
When battery voltage has fallen below the set
value and remains for 20s, It will initiate a warning
alarm signal. Only warning and not to shutdown
the generator.
36
Current Trans.
(5-6000)/5
500
The ratio of external CT
37
Full Load Current
Rating
(5-6000)A
500
Generator’s rated current, used for load over cur-
rent calculating.
38
Over Current Percen-
tage
(50-130)%
120
When the load current has exceeded the set value,
“over current” delay is initiated.