- 24 - 

tousek

  /  E_ST61_07  /  06. 06. 2019

 

Important: preparation works

•  Connect control panels, safety devices to the motor under the safety regulations in .  

Attention: if no stop switch is connected then the terminals 30/31 have to be bridged.

• 

The mechanical limits have to be placed so that contact edges are not  triggered, as this would lead to an 

error message

•  Unlock emergency release of operator and set gate to half-opened position. Then lock the operator again

•  Then turn on the operator (correct connection necessary).

• 

Important:

 Putting into operation in Impulse mode (standard setting) and not in dead man mode.

•  During initial operation the choice of language and operator (SWING X or SPIN 250) is made first, then in the “Basic 

settings” the  adjustment of most important operator settings and after the system test, the automatic detection of limit 

positions of gate is made.

6.  Putting into operation  

Swing gate control unit  ST 61

LANGUAGE SELECTION

• 

Can be selected during initial operation (hence after reset to factory settings).  

• 

Can be also chosen by pressing the ESC button

 ( 

 )

 

for 5s, from any position in menu.

BASIC SETTING

• 

For setting the most important adjustments for initial operation of motor.

• 

Can be selected during initial operation (hence when restoring the factory setting).

• 

All safety devices are activated when leaving factory  

(menu 

 page 7).

• 

The next programming adjustments are made in the main settings menu 

(see 

 6–7).

factory settings

$$$$$$$$$$$$$$$$

$$$$$$$$$$$$$$$$

impulse button

3

$$$$$$$$$$$$$$$$

$$$$$$$$$$$$$$$$

OPEN-STOP-CLOSE

$$$$$$$$$$$$$$$$

$$$$$$$$$$$$$$$$

OPEN-CLOSE-OPEN

change ? YES

confirm

3

4

OPEN

STOP

CLOSE

Select a setting (+/-):

   OPEN/STOP/CLOSE

  OPEN/CLOSE/OPEN

 OPEN

 DEADMAN

OPEN

CLOSE

OPEN

e.g.

return

 

to previous location

putting into operation

(same step after  

factory reset)

5s ESC

(language selection)

$$$$$$$$$$$$$$$$

$$$$$$$$$$$$$$$$

Sprache-language

Deutsch

1

confirm

$$$$$$$$$$$$$$$$

$$$$$$$$$$$$$$$$

Sprache-language

English

scroll

$$$$$$$$$$$$$$$$

$$$$$$$$$$$$$$$$

basic settings

confirmation

3

2

SWING X

SPIN 250

change operator

confirm

$$$$$$$$$$$$$$$$

$$$$$$$$$$$$$$$$

operator 

SWING X

$$$$$$$$$$$$$$$$

$$$$$$$$$$$$$$$$

operator 

SPIN 250

2

OK

Содержание 12111670

Страница 1: ...Connection and installation manual Swing gate control unit ST 61 V 3 0 001 Safety Sensor ...

Страница 2: ...ion of the manual replaces all earlier publications of the same Content General warning and safety notes 3 1 General features control board overview technical data 4 2 Terminal assignment connection notes 5 3 Adjustments overview 6 7 4 Connections and adjustments 8 Buttons switches 8 9 Safety 10 13 Left leaf 16 Right leaf 16 Operating mode 16 17 Light Lamps 18 Peripherals 19 21 Diagnosis 22 5 Conn...

Страница 3: ... purpose for which it has been exclusively designed and which is described in these installation and operating instructions The TOUSEK Ges m b H rejects any liability if the product is used in any way not fully conforming to its original purpose as stated herein Children have to be instructed that the gate facility as well as the belonging parts may not be used improperly e g for playing Furthermo...

Страница 4: ...TSI connection optional tousek connect tousek service Interface E System connector for optional module motor lock or electric lock magnet page 20 VE 230V a c for electric lock magnet module B system connector FE slot for optional radio receiver page 23 ZM slot for optional module status display page 19 T transformer F1 fuse 6 3A F Control board overview Technical data Swing gate control unit ST 61...

Страница 5: ...ver 30 31 32 30 33 34 50 52 53 20 21 22 23 24 25 26 27 0 1 2 10 11 41 42 43 44 45 46 48 80 81 82 83 Warning Before taking off the control cover the main switch must be turned off The inside of the control unit is under tension when power supplied In order to avoid electrical strokes the safety regula tions have to be respected The device may only be connected by qualified per sonnel specialised st...

Страница 6: ...r and choose the language for the menuas and press ENTER Note The language setting can be changed any time by pressing the ESC button for 5s Before you can start programming you have to select the operator SWING X or SPIN 250 The text display informs you on the operating modes selected menus and adjustment of several parameters The programming of the control is done through four but tons ENTER and...

Страница 7: ...0 100 70 soft stop time 0 25s 5s soft start not active active only with SWING X operating mode page 16 17 impulse logic stop start of pause time impulse suppression when opening pause time extension G operating mode impulse mode automatic 1 255s increment 1 partial opening 25 100 100 automatic mode complete partial opening only complete opening only partial opening pause time logic no influence pe...

Страница 8: ...tion OPEN CLOSE OPEN we strongly suggest the installation of a photocell OPEN Only opening commands are accepted by the impulse switch closing the gate with the impulse switch is not possible DEAD MAN The motor opens as long as the impulse switch is pressed hold closing the gate with the impulse switch is not possible As soon as the switch is released the motor stops If hold to run operating mode ...

Страница 9: ...s actuated again during this movement the motor stops With the next impulse the motor moves in opposite direction of the last gate movement OPEN CLOSE OPEN successive impulses Acommand of the pedestrian button makes the according gate wing open close If the button is actuated again during this movement the travel direction is reversed In this operation mode it is not possible to stop the motor wit...

Страница 10: ...ounting notes SYNC function IMPORTANT When using two pairs of photocells please do not install both photocell transmitters receivers on the same side to eleminate interference between both Exception photocells with SYNC function allow the installation of both photocell transmitters receivers on the same side without causing interference to each other Self monitoring of photocells The control unit ...

Страница 11: ...e transmitter receiver transmitter receiver OUTSIDE INSIDE transmitter receiver with active SYNC function Photocells connection examples Important Jumper J of transmitter and receiver has to be adjusted in the same way Outer photocell Tousek LS 26 as safety device Outer reflective photocell Tousek RLS 620 as safety device N O COM N C N O COM N C N O COM N C 48 45 44 43 42 41 46 12 24V J 12 24V NC ...

Страница 12: ...safety sensing edges is made in menu Safety main closing edge 1 term 50 52 and Safety main closing edge 2 term 50 53 If in the menu item operating logic closing edge page 17 one of the modes left right or inside outside is selected this results in the wiring of the safety contact edges to make with each other and the connection to the control terminals Safety sensing edges in mode left right that ...

Страница 13: ...given stop after release open an interruption of the photocell beam during opening or closing makes the motor stop as long as the photocell stays interrupted After release of the photocell the gate opens In automatic mode the gate closes as soon as the pause time has run out in impulse operation another closing command has to be given PHC pause time Safety no influence of photocell the photocell d...

Страница 14: ...ttention Before carrying out any connection works the power supply of the gate facility has to be turned off Operators power supply and sensor cables as well as the capacitors must be connected to the ST 61 control unit acoording to the installation manual The sensor signal defines the performance response when hitting an obstacle or when reaching a gate end position adjustment of sensor sensibili...

Страница 15: ... right 2 1 3 yellow green black blue brown 3 2 1 S M Motor line M to control unit Sensor line S to control unit to control unit SPIN 250 terminals Steuerungsklemmen number colour left operator to terminal right operator to terminal M power supply 4 brown 20 24 5 blue or grey 21 25 6 black 22 26 green yellow 23 27 S Sensor 1 red 65 65 2 blue 66 67 3 black 68 68 Connection SPIN 250 Connection SWING ...

Страница 16: ... as soon as the pause time has run out the gate closes automatically impulse suppression when opening commands which are emitted during the opening movement are suppressed Commands during closing are accepted pause time extension an impulse in automatic operation restarts the pause time If this menu point is chosen the impulse suppression during opening is active at the same time Operating mode Co...

Страница 17: ... and the control unit goes back to automatic mode With this function e g the entrance to a company site can remain open during the day 1st impulseingateopenposition andclosedintheevening 2ndimpulse Thecontrolboardswitchesbacktoautomaticmode autom opening and closing of gate If the gate is in partial open position and permanent open in automatic mode is selected so it is possible to adjust permanen...

Страница 18: ... or when the gate stops it is illuminated During the closing movement it flashes rapidly If the gate is closed the pilot lamp expires illuminates in open position Pilot lamp is illuminated as soon as the gate has reached end position open Before taking off the housing cover the main switch has to be turned off Follow safety instructions page 5 Warning Important Notes regarding connection of a flas...

Страница 19: ...ule optional turn off power supply before installing the additional module Depending on which device e g a courtyard Control lamp is chosen or evaluation of gate status should be effected the corresponding module Z has to be plugged to the according slot plug ZM of control board Additionally the corresponding value has to be selected in menu point Additional module Additional module Courtyard lamp...

Страница 20: ... and closed position of the gate the electric lock only in closed position P1 E VE 72 73 7475 V electric lock 12 or 24Vd c magnet 24Vd c R fix 24V The series resistor R is for tousek magnets GD 50 and GD 70 WARNING Before taking off the housing cover the main switch has to be turned off Follow safety instructions page 5 optional dropbolt module In order to connect the dropbolt SAFELOCK to the cont...

Страница 21: ... 2 dropbolts wire with terminal blocks X Y on the other hand wire it with the dropbolt via connection cable 4 x 0 752 motor connection and limit switch Strictly note the numbering 1 4 of the connection cable s wires for a proper connection Carry out the 230V a c power supply connection on terminal block V and the earthing connection on the earthing screw SAFELOCK control unit with 2 motor prints s...

Страница 22: ...setting Diagnosis NO no reset to factory setting YES reset to factory setting Software version Diagnosis shows the software version and the operator type on the text display Serial number Diagnosis shows the serial number on the text display All inputs OK e g Diagnosis Connections and adjustments The mechanical stops have to be placed so that possibly existing safety contact edges can not be trigg...

Страница 23: ...For programming of receiver please see manual for radio receiver Disconnect the power supply Plug in the receiver printed circuit board E RS433 868 STN1 1 channel or RS433 868 STN2 2 channels into the corresponding slot FE as shown in the picture For range extension an external antenna FK433 or FK868 can be connected 5 Connecting the receiver Swing gate control ST 61 ...

Страница 24: ...ns of gate is made 6 Putting into operation Swing gate control unit ST 61 LANGUAGE SELECTION Can be selected during initial operation hence after reset to factory settings Can be also chosen by pressing the ESC button for 5s from any position in menu BASIC SETTING For setting the most important adjustments for initial operation of motor Can be selected during initial operation hence when restoring...

Страница 25: ...tive change YES adopt 5 left term 50 52 6 mainsafety edge1 mainsafety edge1 active mainsafety edge1 not active change YES adopt 6 left term 50 52 mainsafety edge1 radio edge TX 6 adopt left term 50 52 8 7 mainsafety edge2 mainsafety edge2 active mainsafety edge2 not active change YES adopt 7 mainsafety edge2 radio edge TX 7 adopt right term 50 53 right term 50 53 right term 50 53 ...

Страница 26: ...ft ON change YES motor left OFF adopt 7 8 8 delay left leaf delay left leaf opening delay change YES delay left leaf closing delay adopt 9 9 left operator motor right motor right ON change YES motor right OFF adopt delay right leaf delay right leaf closing delay change YES delay right leaf opening delay adopt right operator right operator 2s 10 11 11 12 12 13 ...

Страница 27: ...tion being detected Close position being detected Ready delay time right delay time right 2s delay time right 10s change YES adopt 14 time 0 25s 15 e g 10s 2s 13 13 14 left motor right motor INSIDE Important The gate installation 1 or with 2 leaves has to reflect in the settings of the main menu Factory setting Operation of swing gate with 2 gate leaves the left and right operator are turned on in...

Страница 28: ...itioning and functions of photocells AR system actuated check force and sensor adjustment safety sensing edge 1 or 2 actuated adjustment of safety sensing edges wrong remove obstacle or function control via status display no reaction of radio receiver radio receiver plugged into wrong connector check proper installation see 5 connection of radio receiver no wrong connected antenna check antenna co...

Страница 29: ... 176 170 265 9 4 210 310 125 8 Dimensioned drawing housing IP54 Swing gate control unit ST 61 dimensions in mm Mounting dimensions back side We reserve the right to change dimensions and technical specifications without prior notice ...

Страница 30: ... 30 tousek E_ST61_07 06 06 2019 Notes ...

Страница 31: ......

Страница 32: ...ic Gliwicka 67 Tel 48 32 738 53 65 Fax 48 32 738 53 66 info tousek pl Tousek s r o Czech Republic CZ 252 61 Jeneč u Prahy Průmyslová 499 Tel 420 777 751 730 info tousek cz We reserve the right to change dimensions and or technical specifications with out prior notice Claims resulting from misprints or errors cannot be accepted tousek PRODUCTS sliding gate operators cantilever systems swing gate op...

Отзывы: