background image

 

 

CONTENTS 

 

 
GENERAL INFORMATION 

 

IMPORTANT SAFETY INFORMATION 

 

 

 

 

 

 

 

 

 

 

POWER REQUIREMENT   

 

 

 

 

 

 

 

 

 

 

 

 

INTRODUCTION 

 

INTRODUCTION 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SITING THE DOOR CONTROLLER 

 

LOCATING THE DOOR CONTROLLER 

 

 

 

 

 

 

 

 

 

 

CABLING   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIMENSIONS   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOOR CONTROLLER PCB CONNECTIONS 

 

PCB WIRING AND LINKS DIAGRAM PCB249ASX 

 

 

 

 

 

 

 

 

CONNECTING A READER 

 

READERS  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIN PAD   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTING A LOCK 

 

FAIL OPEN LOCK 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RELAY CONTACTS   

 

 

 

 

 

 

 

 

 

 

 

 

 

FAIL CLOSED LOCK  

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTING SWITCHES & I/O TO THE DOOR CONTROLLER 

 

OUTPUTS  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 

 

DIGITAL INPUTS 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 

 

AUX IN 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 

 

COMMISSIONING THE DOOR CONTROLLER 

 

CONNECTING POWER 

 

 

 

 

 

 

 

 

 

 

 

 

11 

 

CURRENT CONSUMPTION 

 

 

 

 

 

 

 

 

 

 

 

11 

 

CARE AND MAINTENANCE 

 

BOARD REMOVAL   

 

 

 

 

 

 

 

 

 

 

 

 

12 

 

MEDIA PREPARATION 

 

 

 

 

 

 

 

 

 

 

 

 

12 

 

READER CLEANING  

 

 

 

 

 

 

 

 

 

 

 

 

12 

 

EXAMPLE WIRING FOR EVO DOOR CONTROLLER 

 

2 SEPARATE DOORS 

 

 

 

 

 

 

 

 

 

 

 

 

13 

 

IN AND OUT READER 

 

 

 

 

 

 

 

 

 

 

 

 

16 

Содержание MAN067-06

Страница 1: ...1 EVOLUTION DOOR CONTROLLER UNIVERSAL INSTALLATION AND MAINTENANCE GUIDE MAN067 06 DECEMBER 2018 ...

Страница 2: ...cases a qualified Service Engineer must disconnect the battery before attempting to service the equipment DO NOT DO NOT DO NOT DO NOT continue to operate the equipment if you are in any doubt about it working normally DO NOT DO NOT DO NOT DO NOT remove any cover fastenings unless you are qualified to do so Even then isolate from the power connection before you start DO NOT DO NOT DO NOT DO NOT all...

Страница 3: ...GRAM PCB249ASX 6 CONNECTING A READER READERS 7 PIN PAD 7 CONNECTING A LOCK FAIL OPEN LOCK 8 RELAY CONTACTS 8 FAIL CLOSED LOCK 9 CONNECTING SWITCHES I O TO THE DOOR CONTROLLER OUTPUTS 10 DIGITAL INPUTS 10 AUX IN 10 COMMISSIONING THE DOOR CONTROLLER CONNECTING POWER 11 CURRENT CONSUMPTION 11 CARE AND MAINTENANCE BOARD REMOVAL 12 MEDIA PREPARATION 12 READER CLEANING 12 EXAMPLE WIRING FOR EVO DOOR CON...

Страница 4: ...nicate with the PC The Ethernet cable connection is only accessible when lid is removed All communications is initiated by the door controller which ensures the level of traffic is suitable for shared network systems and reduces network performance limitations Communications is in the form of simple message couplets where each message from the door controller waits for a response from the host NOT...

Страница 5: ...ase Use plastic plugs if screwing to a solid wall CABLING Cabling can enter the door controller from the top or bottom via the case knockouts for cable glands or 20mm conduit entry Communications is via TCP IP connection to the local or wide area network using standard network cable such as CAT5 Manufacturer specified cable should be used to connect between the door controller and the readers PIN ...

Страница 6: ...6 DOOR CONTROLLER PCB CONNECTIONS Reader Power Lock RTE Button PCB249ASX Sounder Reader ...

Страница 7: ...V 12V 12V dependant on link position as shown in the diagram Only change this link if you are sure about the requirements of the reader Factory set at 5V 5V 5V 5V READER CONNECTION DETAILS Please note that wire colours may vary dependant on reader manufacturer and or cable used PIN PAD These are connected where shown and in accordance with the pin pad manual READER TYPE READER TYPE READER TYPE REA...

Страница 8: ...If power fails unexpectedly the lock is also released to leave the door unsecured This type of lock is suitable for the internal doors of a building The drawing above depicts a fail open lock with a monitored break glass triggering input 4 when the break glass is pressed to open door If a break glass unit is not required LK6 can be left connected If a break glass is not used a mechanical method of...

Страница 9: ... of a building although it should be noted that in a handle or break glass should always be provided for emergency egress The drawing above depicts a fail closed lock with monitoring and push button to exit NOTE LK6 LK6 LK6 LK6 is fitted and links 0V 0V 0V 0V to the COM COM COM COM connection of the relay output If two locks are controlled from the same relay it is recommended that one lock is wir...

Страница 10: ... must be moved to other position and the external V V V V connected to the EXT VE EXT VE EXT VE EXT VE connection The external switch or device must be capable of sinking 5mA 5mA 5mA 5mA to operate the input All inputs can be set in the software to be active High or Low This example shows a door switch connected to the internal power supply LK5 LK5 LK5 LK5 must be fitted as shown for this configur...

Страница 11: ...the tie wrap securing the wires ensuring that they are clear of the chassis CURRENT CONSUMPTION The following information should be used as a rough guide only PC898 001 Bar Code Reader 50mA max PP1 481 MIF MifareReader 100mA max PP1 RX4 Universal Reader 250mA max PP8 HPRXP Reader 75mA max PP8 MPROX Reader 75mA max PP1 741 SC Magnetic Stripe Reader 20mA PC190 116 Magnetic Stripe Reader 10mA PC PTPD...

Страница 12: ...fore installing replacement board ensure that all links are fitted in exactly the same positions as on the original board Replace the boards in the reverse order taking care to connect all pins between the satellite board and the main board correctly MEDIA PREPARATION To ensure the best performance from the door controller and associated readers it is essential to use only good quality magnetic st...

Страница 13: ... Maple Barn Beeches Farm Road Uckfield East Sussex TN22 5QD REPAIRS TouchStar ATC Access Time CCTV Unit 49 Vinehall Business Centre Vinehall Road Robertsbridge East Sussex TN32 5JW T 0845 3379 155 E support touchstar co uk W www touchstar atc com ...

Отзывы: