Programming Thermostat Schedules —
Before programming the
thermostat, plan the thermostat daily schedule. The schedule is divided
into 7 days (Monday through Sunday). Each day can have 2 (Occupied 1,
Unoccupied), 3 (Occupied 1, Occupied 2, Unoccupied), or 4 (Occupied 1,
Occupied 2, Occupied 3, Unoccupied) time periods. Each occupied time
period has a start time, stop time , heating set point, and cooling set point.
The unoccupied time period has a heating set point and a cooling set point.
The unoccupied time period is active whenever an occupied time period
is not active. Fill in Table 1 on page 13 as an aid to programming the daily
schedules.
NOTE: When the sensor detects light (the space is occupied), the thermo-
stat will enter into Occupied 1 mode. If the room is dark, the thermo-
stat will follow its programmed schedule. The Occupied 1 schedule should
be turned OFF to keep the thermostat from entering Occupied 1 while the
room is unoccupied. If the Occupied 1 schedule is turned ON, the thermostat
will enter into Occupied 1 per the schedule regardless of light activation. The
Occupied 1 set points are used as the heating and cooling set points during
light activation. The Unoccupied set points should be used as non-work hour
set points (before 8:00 AM and 5:00 PM) when using light activation. For
times when the building is unoccupied during work hours (Monday through
Friday, 8:00 AM to 5:00 PM), the Occupied 2 schedule should be turned ON,
and can be used for moderate energy savings with set points of 80 F for
cooling and 65 F for heating.
PROGRAMMING MODE — To program the daily schedules, perform the
following procedure:
1. Enter programming mode by pressing the Program button. The Occu-
pied 1 annunciator will appear on the thermostat display. See Fig. 5. Use
the UP ARROW and DOWN ARROW buttons to set the maximum num-
ber of Occupied periods available. The thermostat can be set to 1, 2, or
3. After the number of Occupied periods has been selected, press the
Mode button.
2. The cooling set point for Occupied 1 will be displayed. Use the UP
ARROW and DOWN ARROW buttons to raise or lower the cooling set
point until the desired temperature is shown. The range of acceptable
values is 35 to 99 F (1 to 37 C). Press the Mode button to continue. See
Fig. 5.
8