SELECT MOUNTING LOCATION
1. The humidifier should be installed on the supply plenum,
preferably near the coil. Mounting near the evaporative
coil, if applicable, will allow any excess moisture to exit
the system via the condensation drain pan.
2. On vertical equipment allow clearance of the humidifier
and related components such as the water filter and
plastic water live, from the exhaust vent.
3. On vertical equipment, if the nozzle is spraying away
from the coil, there should be a minimum of three feet
from the nozzle to the top of the plenum.
If this is not
available, then point the nozzle of the humidifier
directly into the evaporative coil.
4. Always install downstream of an electronic air cleaner.
Drill or ‘knock out’ a 1” hole & 4 mounting holes for the
#6 screws on the mounting template.
I
NTELLI
M
IST
H
UMIDIFIER
AIR FLOW
HUMIDIFIER
DRAIN
PAN
EVAPORATOR
COIL
PLENUM
FURNACE
HORIZONTAL
EQUIPMENT
HUMIDIFIER
ALTERNATE
LOCATION
ALTERNATE
LOCATION
FURNACE
EVAPORATOR
N-COIL
PLENUM
PLENUM
EVAPORATOR
A-COIL
FURNACE
DRAIN PANS
HUMIDIFIER
VERTICAL
VERTICAL