3. The heating set point for Occupied 1 will be displayed. Use the UP AR-

ROW and DOWN ARROW buttons to raise or lower the heating set point
until the desired temperature is shown. The range of acceptable values
is 35 to 99 F (1 to 37 C). Press the Mode button to continue. See Fig. 4.

4. The cooling set point for Unoccupied will be displayed. Use the UP AR-

ROW and DOWN ARROW buttons to raise or lower the cooling set
point until the desired temperature is shown. The range of acceptable
values is 35 to 99 F (1 to 37 C) or ‘‘OF’’(no unoccupied cooling). To set
the value to ‘‘OF’’, press the UP ARROW button when ‘‘99’’ is dis-
played. Press the Mode button to continue.

5. The heating set point for Unoccupied will be displayed. Use the UP AR-

ROW and DOWN ARROW buttons to raise or lower the heating set point
until the desired temperature is shown. The range of acceptable values
is 35 to 99 F (1 to 37 C) or ‘‘OF’’ (no unoccupied heating). To set the
value to ‘‘OF’’, press the UP ARROW button when ‘‘99’’ is displayed.
Press the Mode button to continue.

6. The day of the week will be shown. Use the UP ARROW and DOWN

ARROW buttons to change the day of the week until the desired starting
day is shown. Possible choices are M (Monday) through S (Sunday).
Press the Mode button when the desired day is shown.

7. The Start Time for Occupied 1 will be displayed. Use the UP ARROW

and DOWN ARROW buttons to raise or lower the time until the desired
Start Time is shown. Press the Mode button to continue. See
Fig. 5.

8. The Stop Time for Occupied 1 will be displayed. Use the UP ARROW

and DOWN ARROW buttons to raise or lower the time until the desired
Stop Time is shown. Press the Mode button.

9. The On/Off icon will be displayed. Use the UP ARROW to turn the Oc-

cupied 1 period ON for this day. Use the DOWN ARROW to turn the
Occupied 1 period OFF for this day. If the schedule is set to OFF, the
thermostat will follow the Unoccupied set points.

10. Repeat Steps 2 through 9 to program the remaining schedule for occu-

pied periods 2 and 3 (if selected in Step 1).

9

Содержание CPE230RF

Страница 1: ...tch External Device 13 Two Stage Operation 13 Fan Operation 13 IMPORTANT Read entire instructions before programming the thermostat OWNER S MANUAL CPE230RF Commercial Programmable Thermostat Wireless Transmitter Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION R CARRIER CO...

Страница 2: ...ore than one transmitter is used with a single receiver the transmitters must be given different Unit ID Numbers Only the transmitter with Unit ID Number 1 may have a programmed schedule or be configured All configu ration parameters are taken from the transmitter with Unit ID Number 1 Trans mitters with Unit ID Numbers 2 3 and 4 cannot be programmed or config ured except for set points When more ...

Страница 3: ...N ON or blank override indication room temperature desired temperature time of day day of the week schedule period Occupied 1 2 or 3 Unoccupied setup indicator used in programming mode lock indicator start indicator used in programming mode Transmitter Indicator A transmitter indicator is located in the middle of the transmitter See Fig 2 The indicator will be lit if the transmitter is sending a s...

Страница 4: ...ng or cooling to meet the heating or cooling temperature set point If the thermostat is in AUTO mode pressing the UP ARROW or DOWN ARROW buttons will adjust both the heating and cooling set points Pressing the UP ARROW or DOWN ARROW buttons in Cooling mode will adjust only the cooling set points Pressing the UP ARROW or DOWN ARROW buttons in Heating mode will adjust only the heating set points The...

Страница 5: ...perature and the heating and cooling set points The thermostat will provide automatic changeover from Heating to Cooling mode and Cooling to Heating mode when required The thermostat will auto matically switch to maintain the desired temperature setting The ther mostat does not need to be manually changed from heating to cooling or cooling to heating operation If PROGRAM ON is selected your daily ...

Страница 6: ... to the Set Clock section on page 7 for more information OVERRIDE BUTTON The Override button is used to force the thermo stat from Unoccupied mode into the Occupied 1 mode comfort settings The Override period will be set at 30 minutes The thermostat will then return to Unoccupied mode To increase the amount of time in Override mode press the Override button again Thirty minutes of override time wi...

Страница 7: ... ensure the schedules are properly fol lowed make sure that AM or PM is correct for the time chosen When the correct time is shown press the Mode button to modify the day of the week The current day will blink on and off Press the UPARROW and DOWN ARROW buttons until the correct day is shown Press and hold the Mode and Override buttons for 2 seconds again to exit the Set Clock mode The transmitter...

Страница 8: ...ng mode by pressing the Mode and UP ARROW but tons at the same time The Occupied 1 annunciator will appear on the thermostat display See Fig 5 Use the UP ARROW and DOWN AR ROW buttons to set the maximum number of Occupied periods avail able The thermostat can be set to 1 2 or 3 After the number of Oc cupied periods has been selected press the Mode button 2 The cooling set point for Occupied 1 will...

Страница 9: ...ating To set the value to OF press the UP ARROW button when 99 is displayed Press the Mode button to continue 6 The day of the week will be shown Use the UP ARROW and DOWN ARROW buttons to change the day of the week until the desired starting day is shown Possible choices are M Monday through S Sunday Press the Mode button when the desired day is shown 7 The Start Time for Occupied 1 will be displ...

Страница 10: ... points for each day have been entered press the Program button to finish entering the schedule NOTE The thermostat will continue to follow the schedule until a new one is entered If only one occupied schedule is selected the Occupied 2 and 3 schedules are skipped If the start time is set later in the day than the stop time the program will run from midnight of that day to the stop time and then f...

Страница 11: ...Fig 5 Start Time Display Fig 6 Copy Command Display 11 ...

Страница 12: ...ed 1 Occupied 2 Occupied 3 Unoccupied Start Stop Heat Cool Start Stop Heat Cool Start Stop Heat Cool Heat Cool Monday Tuesday Wednesday Thursday Friday Saturday Sunday NOTE The cooling temperature set point must be higher than the heating temperature set point 12 ...

Страница 13: ...n the desired temperature setting The thermostat does not need to be manually changed from heating to cooling or cooling to heat ing operation Electric Heat When the Electric Heat DIP switch at the receiver is set to ON the thermostat will turn on the fan immediately any time there is a heat demand This feature should only be used on electric heating applica tions Do not use with gas heat Dry Cont...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...argest manufacturer of air conditioning heating and refrigeration products Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION R CARRIER CORPORATION 10 98 LITERATURE NUMBER P474 6SO PRINTED IN CHINA ...

Отзывы: