About Advanced Features & Operation

Page 15

MEMORY BACKUP - In the event of a power loss, the 
       thermostat will retain the stored program settings without
       external power or batteries.
       

2 STAGE OPERATION - The 2nd Stage of heat or cool is
       turned on when (

1

) the 1st Stage has been on for a

       minimum of two minutes, 

and

 (

2

) the temperature spread

       from the setpoint is equal to or greater than: 

the setpoint

       plus the deadband, plus 2 degrees.

Heat

Setpoint

Cool

Setpoint

Dead
Band

Dead
Band

2 degrees

1st Stage

turn on

2nd Stage

turn on

1st Stage

turn on

Heating

Cooling

MINIMUM HEAT/COOL SETPOINT DIFFERENCE - The Heat
       and Cool setpoints will not be allowed to come any closer
       to each other than the value set in Advanced Setup 

step

       

# 8, on page 12

.  This minimum difference is enforced

       during Auto changeover 

operation.

         
        

and Program On 

Содержание 1 For All P374-1000FM

Страница 1: ...y Thermoglow Backlight Dual or Single Setpoint No Batteries Required Outdoor Temperature Sensor Available 1 For All Use with most Air Conditioning Heating Systems including 1 Stage Electric Cooling or...

Страница 2: ...eriods ADVANCED SETUP ABOUT ADVANCED OPERATION WARRANTY Page 1 CAUTION Follow Installation Instructions before proceeding SET THERMOSTAT TO MODE OFF PRIOR TO CHANGING SETTINGS IN SETUP OR RESTORING FA...

Страница 3: ...Front Panel Page 2 Liquid Crystal Display with Thermoglow Up Down Buttons Mode Button Fan Button Heat or Cool Indicator Heat Red Cool Green Temperature Sensor Bubble 1 2 3 4 5 6 1 3 5 2 4 6...

Страница 4: ...heat and cool modes as the temperature varies OFF indicates the entire system is turned off PROGRAM ON indicates the stored program is enabled to run Page 6 Clock Indicates the current time of day Thi...

Страница 5: ...up Indication Indicates the thermostat is in the Advanced Setup mode Page 11 Fan Operation Indication Fan On indicates constant continuous fan operation When Fan On is not lit indicates the fan will o...

Страница 6: ...Go Page 5 The thermostat is preprogrammed from the factory to operate 1 or 2 Stage equipment without the need for further programming To optimize the installation of this thermostat follow the instruc...

Страница 7: ...ndicates both heating and air conditioning systems are turned off AUTO will automatically select heat or cool based on room temperature demand Program On will activate the stored timer operation Morni...

Страница 8: ...ons in Heat or Cool modes will adjust only the Heat or Cool set temperature To select desired temperature in Single Setpoint please also refer to page 17 Select Desired Temperature Page 7 Basic Operat...

Страница 9: ...ming Continued MODE MODE MODE MODE 74 COOL 74 72 COOL HEAT Adjust the start time for Morning Adjust the heating setpoint for Morning Adjust the cooling setpoint for Morning 35 99 35 99 Am Am Am 7 30 7...

Страница 10: ...Adjust the start time for Evening Adjust the cooling setpoint for Evening Adjust the start time for Day Adjust the heating setpoint for Day Adjust the cooling setpoint for Day 35 99 35 99 35 99 Am I0...

Страница 11: ...0 78 HEAT COOL Pm I i 30 Night Programming 4 Time Periods Adjust the heating setpoint for Night Adjust the heating setpoint for Evening Adjust the cooling setpoint for Night Adjust the start time for...

Страница 12: ...y press and hold the Fan button in and press the up or down buttons FAN MODE Select 1 Day Programmable ON or Non Programmable OFF On Off Select Single setpoint or Dual setpoint operation 1 Single Setp...

Страница 13: ...n in step 4 B O 81f Select Electric Heat On or Off Step 6 only appears if heat pump is off in step 4 On Off Adjust the deadband from 1 6 degrees Adjust the minimum difference between cooling heating s...

Страница 14: ...s per hour limit defeated d1 d defeat 5 min Compressor lockout d d1 2 6 6 9 Cy Setup Select thermostat operation in degrees Fahrenheit or Centigrade C F F I I Setup MODE FAN Press Press the Mode butto...

Страница 15: ...ammable Off On On 3 Display Mode 1 2 2 4 5 6 7 8 9 10 11 Heat Pump Off On Off Reversing Valve polarity O B O Electric Heat Off On Off Deadband or Temperature swing 1 6 1 Forced minimum difference heat...

Страница 16: ...2 the temperature spread from the setpoint is equal to or greater than the setpoint plus the deadband plus 2 degrees Heat Setpoint Cool Setpoint Dead Band Dead Band 2 degrees 1st Stage turn on 2nd Sta...

Страница 17: ...a feature available to Heat Pump installations To turn on Emergency Heat press in the Fan button While holding the Fan button press Up button for 2 seconds The Cool setpoint display will read EH Duri...

Страница 18: ...and is above and below the setpoint To avoid short cycling in single setpoint it is recommended to raise the deadband to a minimum of 2 page 12 step 7 Press and hold the Mode button for 2 seconds to d...

Страница 19: ...eat and Cool setpoints will remain spread apart by the amount that they were adjusted prior to entering Auto For example If the Cool setpoint was set to 80 while in the Cool mode and the Heat setpoint...

Страница 20: ...n NOTE CAUTION ON PAGE 1 OUTSIDE SENSOR Optional Accessory When connected to terminals RS 5 RS GND on the back of the thermostat the thermostat will read the temperature from the Outside not control t...

Страница 21: ...RK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS AL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF...

Отзывы: