background image

Important recommendations

 Never allow an exposed flame or spark  near the 

batteries, particularly while charging.

 Never smoke while performing any operation 

on the battery.

 For protection, wear rubber gloves, long 

sleeves and appropriate splash goggles or face 
shield.

 The electrolyte is harmful to skin and eyes. In 

the event of contact with skin or eyes, wash 
immediately with plenty of water. If eyes are 
affected, flush with water and obtain 
immediate medical attention.

 Remove all rings, watches and other items with 

metal parts before working on the battery.

 Use insulated tools.
 Avoid static electricity and take measures for 

protection against electric shocks.

 Discharge any possible static electricity from 

clothing and/or tools by touching an earth-
connected part "ground" before working on 
the battery.

1. Receiving the shipment

Unpack the battery immediately upon arrival. Do 
not overturn the package. Transport seals are 
located under the cover of the vent plug. The 
battery is normally shipped filled and ready for 
installation.

 Make sure all items have been received by 

comparing with the packing list. 

 Check for damage or electrolyte spillage. 

Report any irregularities to the carrier and to 
Saft.

 Remove the plastic transport seals. The battery 

must never be used electrically with the plastic 
transport seal in place as this can cause 
permanent damage.

The battery is ready for installation.

2. Storage

Store the battery indoors in a dry, clean, cool 
location (0°C to +30°C / +32°F to +86°F). 

 Make sure that the transport seals remain in 

place during storage.

 Do not store in direct sunlight or exposed to 

excessive heat.

 A battery delivered charged (80 %) must not be 

stored more than 3  months up to 30°C, or 
more than 6 months up to 20°C (including 
transport).  If a charged battery has to be 
stored  for more than the durations and 
associated temperatures mentioned above, 
discharge the cells at 0.2 C

5

A down to 1V per cell or less. 

SRA/SRA LT/SRA HT Ni-Cd Batteries 

Installation and operating instructions

 A battery delivered discharged and filled may 

be stored for many years before it is installed. 

 If storage is required prior to commercial 

service, clean and coat the metallic parts with a 
thin layer of neutral vaseline or neutral 
petroleum jelly grease approved by Saft. Leave 
the battery in its transport case to protect from 
dust, moisture and short circuits.

3. Installation

Remove the transport seals and close the vent 
plugs.

3.1. 

Verify that cells are correctly interconnected 

and that battery connection to the load is also 
correct.

3.2. 

Check tightness of terminal connecting nuts. 

Torque applied must be:
•  10 ± 2 N.m for cells  

SRA 75 to140 
SRA LT 75 to140 
SRA HT 70 to130

•  30 ± 3 N.m for cells  

SRA 160 to 375 
SRA LT 160 to 375 
SRA HT 150 to 350

The connectors and terminal nuts should be 
corrosion-protected by coating with a thin layer 
of DW33 anti-corrosion greasy film.

3.3. 

Electrolyte

The electrolyte used is specific for each product 
line:
•  SRA: E 41
•  SRA LT: E 34
•  SRA HT: Na 15 L

4. Commissioning

Caution:  during constant charging operations, 
the battery box must be open.

4.1.

 The cells are delivered 80 % charged.

Charging and discharging should be done at 
constant current.

 For a battery stored less than 3 months at T< 

+30°C, or less than 6 months at T< +20°C, 
no charge/discharge operation is required 
before use.

 For a battery stored for more than 3 months or 

at T>+30°C, or more than 6 months at 
T>+20°C :

•  Discharge the battery at 0.2 C

5

A down to an 

average 1V per cell. 

•  Maintain the battery in open circuit during 8 

hours or until the battery temperature is 
between 10°C and 30°C. 

•  Charge the battery at 0.2 C

5

A for 8 hours.

4.2.

 The cells are delivered discharged

Caution: even if the battery is discharged, there 
remains a residual charge that may cause an 
electric shock. 
Charging and discharging should be done at 
constant current. 

 For a battery placed into service immediately 

after delivery or after less than one year of 
storage:

• Preferred solution:  constant current charge; 

charge the battery at 0.2 C

5

A for 8 hours.

  Caution: during constant current charging the 

battery box must be open.

•  Constant voltage charge: 1.55V/cell for 

20 hours with the current limited at 0.2 C

5

A.

 For a battery stored for more than 1 year: 

•  Charge the battery at 0.2 C

5

A for 8 hours. 

•  Discharge the battery at 0.2 C

5

A down to an 

average 1V per cell. 

•  Maintain the battery in open circuit during 8 

hours or until the battery temperature is 
between 10°C and 30°C. 

•  Charge the battery at 0.2 C

5

A for 8 hours. 

The battery is ready for use.

5. Charging in service

 1.47 V/cell at +20°C (+68°F) with voltage 

compensation: 
- 3 mV/°C/cell (-1.7 mV/°F/cell).
For higher charging voltages, consult your local 
Saft representative.

 Boost charge according to IEC62973-2.

6. Topping-up

Frequency of topping-up must be determined for 
each battery. Topping-up shall be performed 
after the first year in order to determine the ideal 
topping-up interval which depends on the 
charging voltage and actual use of the battery. 
Never let the electrolyte level fall below the 
minimum level mark. Use only distilled or 
deionized water to top-up. 
If charge at constant current : operation must be 
carried on charged cells with a rest time of 