Page:  2

1.  Never install telephone wiring during a lightning storm.
2.  This product is for 

INDOOR USE ONLY

.

3.  TLP Series suppressors are intended for use on the equipment side of UL 497 listed 

Primary Protectors.

4.  Read and understand all instructions prior to installation and operation.

CAUTION - IMPORTANT SAFETY INSTRUCTIONS

INSTALLATION

WARNING

Should your equipment or building be subject to a direct lightning strike, this product may not
provide complete protection.

Page:  3

The 

TLP Series

of products is easy to install.  The following instructions clearly explain each step:

NOTE:

Make sure you follow the installation instructions exactly; if the suppressor is improper-

ly installed, the current limiting feature could be rendered inoperable.

A.  TLP Modular Jack Interface Models:

1. Connect the Load (protected) Side of the 

TLP Series

product to your communications       

equipment using a straight through modular, twisted pair, cable of the shortest possible 
length.

Note

:  RJ Jacks used on the TLP-RJ Series are  8 position RJ45.

2. Connect your incoming (unprotected) telephone cable to the Line (unprotected) Side of the 

TLP Series

product.

3. Connect a #14 AWG ground wire from one of the unit's securing screws and secure 

it to the nearest available chassis ground.

B.  TLP Terminal Block Interface Models:

1. Connect the Load (protected) Side of the 

TLP Series

product to your communications       

equipment using straight wire hookups as short as possible.

2. Connect your incoming (unprotected) telephone cable to the Line (unprotected) Side of the 

TLP Series

product.

3. Connect a #14 AWG ground wire from the unit's ground stud and secure it to the near

est available chassis ground.

GROUNDING

NOTE:

If you have any questions as to how your equipment is grounded, consult the

manufacturer’s user manual(s).

The unit's ground stud must be connected to the ground reference used by the system being pro-
tected.  In a computer room environment this grounding point may be the ground bar in the AC
power panel.  Ground leads longer than 12" are not recommended.

PERFORMANCE NOTE

The grounding wire must be as short as possible.  Minimize length to the centimeter/inch and use
a minimum of No.14 AWG wire.

INDEPENDENT GROUNDS

Surge protection devices must not be connected to ground points that are independent of AC
ground.

NOTE:

The protected device/equipment should also have AC protection because it is still

vulnerable to transients on the power lines.  Omitting AC protection poses a continued threat of
failures at the communication interface.

CASE B

The TLP Series is offered in 2 Case Sizes. Each unit is provided with a universal mounting
bracket and a Din Rail clip(s).  The bracket enables units to be mounted in several different
planes as shown in the drawings.

The Din Rail clip is not necessary when mounting units to hard surfaces, however should you
want to mount the device to a din rail, the clip mates to a standard DIN 35 Rail.

MOUNTING INFORMATION

Grounding is accomplished via any of the four corner securing screws on the units.  When the
din rail clip is used it will pick up a ground connection becoming part of the unit’s ground. A
ground lug is also provided and can accomodate up to a #10 AWG ground wire. The ground lug
can be secured to any one of the four corner screws in order to obtain a ground point. 

NOTE:

It

is always best to test grounds to verify their existence before relying on them to protect sensitive
equipment.

CASE A

Mounting
Bracket

Attaching The Din
Rail Mounting
Clip:

1. Remove Nut From Desired
Stud Location.
2. Spin Din Clip on to the Stud.
3. Replace Nut & Secure

.

Attaching The
Mounting Bracket:

1. Remove Nuts From Case Studs.
2. Place Bracket on to Studs.
3. Replace Nuts & Secure

.

Combination Use:
Mounting Bracket
& Din Rail Clip:

1. Secure Din Clip To
Mounting Bracket
With Hardware
Provided
2. Remove Nuts From
Case Studs.
3. Place Bracket onto
Studs.
3. Replace Nuts &
Secure

.

MATERIALS 

1 TLP Unit
1 Din Clip 
1 Mounting Bracket
1 Screw

MATERIALS 

1 TLP Unit
2 Din Clips 
1 Mounting Bracket
2 Screws

Din Clips

Combination Use: Mounting
Bracket & Din Rail Clip:

1. Secure A Din Clip To The Mounting
Bracket With Hardware Provided
2. Remove Nuts From Case Studs.
3. Place Bracket onto Studs.
4. Replace Nuts & Secure

.