INSTALLING THE OUTDOOR UNIT

INSTALLER

BLEEDING

INSTALLER

10

Do not install the outdoor unit in pits or air vents

Installing the pipes

Use suitable connecting pipes and equipment for 

the refrigerant R410A.

Wrap all the refrigerant pipes and joints.
Tighten the connections using two wrenches wor-

king in opposite directions.

Vacuum pump

Humid air left inside the refrigerant circuit can cause com-

pressor malfunction. After having connected the indoor

and outdoor units, bleed the air and humidity from the

refrigerant circuit using a vacuum pump.
(1) Unscrew and remove the caps from the 2-way and 3-

      way valves.

(2) Unscrew and remove the cap from the service valve.

(3) Connect the vacuum pump hose to the service valve.

(4) Operate the vacuum pump for 10-15 minutes until an

      absolute vacuum of 10 mm Hg has been reached.

(5) With the vacuum pump still in operation, close the 

      low-pressure knob on the vacuum pump coupling.

      Stop the vacuum pump.

(6) Open the 2-way valve by 1/4 turn and then close it

      after 10 seconds. Check all the joints for leaks using

      liquid soap or an electronic leak device.

(7) Turn the body of the 2-way and 3-way valves. Discon-

      nect the vacuum pump hose.

(8) Replace and tighten all the caps on the valves.

Vacuum pump

Vacuum pump

Location

Twisting moment (N.m)

35-40
60-65
45-50
70-75

Φ12
Φ19

Diameter (mm) 

Φ9.52

Φ16

15-20

Φ6

18

、 、

24

42K

36

Caution: Installation Must be Performed in 

Accordance with the NEC/CEC by Authorized 

Personnel Only.

conversion joint

INDOOR

UNIT

Connect to the

indoor unit

Refrigerant fluid di

rection of fiow

3-w

ay valve

2-w

ay valve

inlet

(2)Turn

(8) Secure

(7)Turn to open fully

(2)Turn

(8) Secure

(6) Open by 1/4 turn

(7)Turn to open fully

(2)Turn

(8) Secure

V

alve cap

Valve cap

Service

The refrigerant pipes must not exceed the maximum

heights 10m(18Kx2&24Kx2&24Kx3&36x2&36x3&36

x4&42x2&42x3&42x4&42x5).

Use bolts to secure the unit to a flat, solid floor.

When mounting the unit on a wall or the roof, make

sure the support is firmly secured so that it cannot

move in the event of intense vibrations or a strong

wind.

Install the drain fitting and the drain hose

(for model with heat pump only)

Condensation is produced and flows from the out-

door unit when the appliance is operating in the 

heating mode. In order not to disturb neighbours 

and to respect the environment,install a drain fitting 

and a drain hose to channel the condensate water.

Install the drain fitting and rubber washer on the 

outdoor unit chassis and connect a drain hose to it 

as shown in the figure.

Models(m)

18Kx2

36Kx2 36Kx3

Max. connection pipe length 50

Max. connection pipe length

(Simple one indoor unit)

25

24Kx2 24Kx3

50
25

50
25

70

25

75
25

Models(m)

36Kx4

42Kx4 42Kx5

Max. connection pipe length 75

Max. connection pipe length

(Simple one indoor unit)

25

42Kx2 42Kx3

50

25

80

25

75
25

80

25

unit need to be installed the indoor unit 

Содержание TM18H5O

Страница 1: ...8OWUD HDW 0XOWL RQH TM24H5O TM18H5O TM42H5O TM36H5O ...

Страница 2: ...some models without displayer the position and shape of the displayer please refer to the real one In line with the company s policy of continual product improvement the aesthetic and dimensional characteristics technical data and accessories of this appliance may be changed without notice This appliance is not intended for use by persons including children with reduced physical sensory or mental ...

Страница 3: ...tructed in this booklet These instructions are not intended to cover every possible condition and situation As with any electrical household appliance common sense and caution are therefore always recommended for installation operation and maintenance Instructions for installation and use of this product are provided by the manufacturer Indicates a hazardous situation that if not avoided will resu...

Страница 4: ... turned on or off according to your requir ement automatically please do not turn on or turn off the unit freque ntly otherwise disadvantage effect may be caused to the unit Rated voltage of this air conditi oner 208 230V 60Hz The com pressor will vibrate sharply if the voltage is too low resappointed amage to refrigerating system Electrical component are easy to damage if the voltage is too high ...

Страница 5: ... of the units that have been purchased No Description 1 Air outlet grille 2 Valve OUTDOOR UNIT 1 2 The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube Be sure to cut off the power supply before cleaning the air conditioner otherwise electric shock might happen Wetting of air conditioner may cause the risk of electric shock Make sure n...

Страница 6: ...the appearance of air conditioner Only use soft dry cloth moist cloth clean the air conditioner cabinet Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard Note The above figu...

Страница 7: ... 920 380 790 MODE 208 230V 60Hz mm2 40 5 3 Electrical data Electricity supply Size and clearance A P L H Minimum power cord section mm mm mm L P H Fuse or air switch 1016 440 1103 MODE 208 230V 60Hz mm2 TM36H5O TM42H5O 60 8 4 Electrical data Electricity supply Size and clearance TECHNICAL DATA GENERAL INFORMATION OUTDOOR UNIT WORKING TEMPERATURE RANGE GENERAL INFORMATION 5 Maximum cooling Maximum ...

Страница 8: ...n all pole disconnection switch having a contact separation of at least 3mm in all pole should be connected in fixed wiring The connection pipes and the connection wirings of the unit A and unit B must be corresponding to each other respective The appliance shall be installed in accordance with national wiring regulations TM18H5O TM18H5O Including an air switch with suitable capacity please note t...

Страница 9: ...re wire has been fixed well 5 Install the handle 1 Remove the handle at the right side plate of the outdoor unit one screw Note The above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased Including an air switch with suitable capacity please note the following table Air switch should be included magnet b...

Страница 10: ...door unit one screw Note The above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased Wrong wire connection may cause malfunction of some electric components After fixing cable ensure that leads between connection to fixed point have some space An all pole disconnection switch having a contact separation ...

Страница 11: ... and the connection wirings of the unit A unit B unit C and unit D unit E must be corresponding to each other respective The appliance shall be installed in accordance with national wiring regulations Including an air switch with suitable capacity please note the following table Air switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Ca...

Страница 12: ...Φ9 52 Φ16 15 20 Φ6 18 24 42K 36 Caution Installation Must be Performed in Accordance with the NEC CEC by Authorized Personnel Only conversion joint INDOOR UNIT Connect to the indoor unit Refrigerant fluid direction of fiow 3 way valve 2 way valve inlet 2 Turn 8 Secure 7 Turn to open fully 2 Turn 8 Secure 6 Openby 1 4 turn 7 Turn to open fully 2 Turn 8 Secure Valve cap Valve cap Service The refrige...

Страница 13: ...edby trained and qualified person Do not use any other refrigerant than R410A MAINTENANCE INSTALLER INSTALLATION DIMENSION DIAGRAM INSTALLER 11 TM24H5O TM18H5O TM36H5O TM42H5O Space to the cover 200cm 30cm 50cm Air inlet side or above or above Space to the wall Air outlet side or above 30cm or above or more Space to the cover 50cm Space to the cover 200cm 30cm 50cm Air inlet side or above or above...

Страница 14: ...nits Have the length of refrigerating pipe and refrigerant charge amount been recorded Has the unit been safely grounded Problems Owing to Improper Installation The unit may drop vibrate or make noises May cause unsatisfactory cooling heating effect May cause condensation and water dropping May cause condensation and water dropping The unit may bread down or the components may be burned out The un...

Страница 15: ......

Страница 16: ...66129932312 ...

Отзывы: