WX9 ASD Installation and Operation Manual
79
ST Signal Selection
Program
Terminal
Input Special Functions
This parameter is used to set the operation of the
Standby
(
ST
) control terminal
or any terminal configured as the
ST
terminal.
Settings:
0 — Standard
1 — Always On
2 — Interlock with F/R Terminal
The
Standard
setting enables the ASD for operation so long as the control
terminal
ST
is connected to
CC
via a jumper, contact, or other means.
The
Always On
setting allows the ASD to operate without the
ST
-to-
CC
connection. The control terminal
ST
may be configured for another function or
unused.
The
Interlock with F/R Terminal
setting configures the
F
(
Forward
) and
R
(
Reverse
) control terminals for the secondary function of
Standby
. Closing a
set of contacts to either
F
or
R
will cause the ASD to accelerate the motor to the
programmed setpoint of
F
or
R
. Opening the
F
and
R
contact will disable the
ASD and the motor will coast to a stop. The control terminal
ST
may be
configured for another function or unused.
Direct Access Number — F103
Parameter Type —
Selection List
Factory Default —
Standard
Changeable During Run —
No
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......