WX9 ASD Installation and Operation Manual
17
Connecting the ASD
Contact With Three-Phase Input/Output Terminals May Cause An
Electrical Shock Resulting In Injury Or Loss Of Life.
Refer to the section titled
Installation Precautions on pg. 4
and the section titled
before attempting to connect the ASD and the motor to electrical power.
Power Connections
for a system I/O connectivity schematic.
R/L1
,
S/L2
, and
T/L3
are the three-phase input supply terminals for the ASD.
U/T1
,
V/T2
, and
W/T3
are the output terminals of the ASD that connect to the motor.
Connect the input and output power lines of the ASD as shown in
An inductor (DCL) may be connected across the
PO
and
PA/+
terminals to provide additional filtering.
When not used, a jumper must be connected across these terminals.
PA/+
and
PB
are used for the DBR connection if using a braking resistor (
not used with the WX9
ASD
).
PC/-
is the negative terminal of the DC bus.
Ensure that the ASD power has been turned off and wait at least the minimum time indicated on the
enclosure-mounted label before coming into contact with any circuits.
Power Connection Requirements
Connect the three-phase input power of the correct voltage to the input terminals of the ASD at
R/L1
,
S/
L2
, and
T/L3
(see
for the typical electrical connection scheme and
for the
terminal locations).
Connect the output of the ASD to the motor from the ASD terminals
U/T1
,
V/T2
, and
W/T3
. The input
and output conductors and terminal lugs used shall be in accordance with the requirements listed in the
section titled
Voltage/Current Specifications on pg. 202
.
Install a molded case circuit breaker (MCCB) or fuse between the three-phase power source and the
ASD in accordance with the fault current setting of the ASD and the
NEC
Article 430
.
The ASD is designed and tested to comply with UL Standard 508C. Modifications to the ASD system
may disqualify the UL rating.
As a minimum, the installation of the ASD shall conform to the NEC Article 110 (“Requirements for
Electrical Installations”), all regulations of the Occupational Safety and Health Administration, and any
other applicable national, regional, or industry codes and standards.
Note:
In the event that the motor rotates in the wrong direction when powered up, reverse
any two of the three ASD output power leads (U, V, or W) connected to the motor.
DANGER
CAUTION
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......