160
WX9 ASD Installation and Operation Manual
Over-Torque Trip Selection
Program
Protection
Over-Torque Parameters
This parameter Enables/Disables the
Over-Torque Tripping
function.
When enabled, the ASD trips if an output torque value greater than the setting
of
exists for a time longer than the setting of
.
When disabled, the ASD does not trip due to over-torque conditions.
Note:
A discrete output terminal may be activated when an over-torque
alarm occurs if so configured (see
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F615
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Over-Torque Detection Level During Power Running
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping. This setting is a percentage of the maximum rated torque of the
drive.
This function is enabled at
Over-Torque Trip Selection
).
Direct Access Number — F616
Parameter Type —
Numerical
Factory Default —
150.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Over-Torque Detection Level During Regenerative Braking
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping during regeneration. This setting is a percentage of the
maximum rated torque of the drive.
This function is enabled at
Over-Torque Trip Selection
).
Direct Access Number — F617
Parameter Type —
Numerical
Factory Default —
150.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Over-Torque Detection Time
Program
Protection
Over-Torque Parameters
This parameter sets the amount of time that the over-torque condition may
exceed the tripping threshold level set at
before a trip occurs.
This function is enabled at
.
Direct Access Number — F618
Parameter Type —
Numerical
Factory Default —
0.50
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — Seconds
Cooling Fan Control
Program
Protection
Special Protection Parameters
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
Direct Access Number — F620
Parameter Type —
Selection List
Factory Default —
Automatic
Changeable During Run —
Yes
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......