WX9 ASD Installation and Operation Manual
147
VI/II Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the gain of the
VI/II
input terminals.
Note:
See note on
for additional information on the VI/II
terminal.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
Direct Access Number — F471
Parameter Type —
Numerical
Factory Default —
156
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
RR Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the bias of the
RR
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and either increasing or
decreasing this setting to provide an output of zero from the ASD.
Direct Access Number — F472
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
RR Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the gain of the
RR
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
Direct Access Number — F473
Parameter Type —
Numerical
Factory Default —
184
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
RX Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the bias of the
RX
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and either increasing or
decreasing this setting to provide an output of zero from the ASD.
Direct Access Number — F474
Parameter Type —
Numerical
Factory Default —
99
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......