112
WX9 ASD Installation and Operation Manual
PG Reference Point 1
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
PG
input
terminal when it is used as the
Speed/Direction
control input. The
PG
input
signal is a pulse count originating from a shaft-mounted
Encoder
.
Note:
See Instruction Manual P/N 58687 for additional information on
the
PG Option Board
.
PG Speed Control Setup
Perform the following setup to allow the system to receive a binary control
input:
•
Program
Fundamental
Standard Mode Selection
Command
Mode Selection
any setting).
•
Program
Fundamental
Standard Mode Selection
Frequency
Mode 1
Pulse Input Option
.
•
Set
PG Point 1 Frequency
).
•
Set the
PG
PG Reference Point 1
.
•
Set
PG Point 2 Frequency
).
•
Set the
PG
PG Reference Point 2
•
Provide a
Run
command (F or R).
Once set, as the
PG
input pulse count changes, the directional information or
the output frequency of the drive will vary in accordance with the above
settings.
This parameter sets the
PG
input pulse count that represents
Reference Point 1
(frequency)
(direction/speed). The range of values for this parameter is -100 to
+100% of the
PG
input pulse count range.
Note:
Further application-specific
PG
settings may be performed from
the following path: Program
Feedback
PG Settings
Direct Access Number — F234
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -100.00
Maximum — +100.00
Units — %
Frequency Settings
PG Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
PG
input
terminal when it is used as the
Speed/Direction
-
Control
input.
This parameter sets
PG Point 1 Frequency
and is the frequency that is
associated with the setting of
PG Reference Point 1
).
See
PG Reference Point 1
)
for additional information on this setting.
Direct Access Number — F235
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — - (Maximum Freq. (
Maximum — + (Maximum Freq. (
))
Units — Hz
PG Reference Point 2
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
PG
input
terminal when it is used as the
Speed/Direction
-
Control
input.
This parameter sets the
PG
input pulse count that represents
PG Reference
Point 2
(direction/speed). The range of values for this parameter is -100 to
+100% of the
PG
input pulse count range.
See
PG Reference Point 1
)
for additional information on this setting.
Direct Access Number — F236
Parameter Type —
Numerical
Factory Default — +
100.00
Changeable During Run —
Yes
Minimum — -100.00
Maximum — +100.00
Units — %
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......