102
WX9 ASD Installation and Operation Manual
Frequency Mode 2
Program
Fundamental
Standard Mode Selection
This parameter selects the source of the frequency command signal to be used
as
Frequency Mode 2
in the event that
Frequency Mode 1
is disabled or if
Frequency Mode 2
is set up as the primary control parameter.
See
Frequency Mode 1
and
Frequency Priority Selection
(
for
additional information on this setting.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — CN8 Option
6 — Binary/BCD (Option)
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Option Board
10 — UP/DOWN Frequency
11 — Pulse Input (Option)
Direct Access Number — F207
Parameter Type —
Selection List
Factory Default —
VI/II
Changeable During Run —
Yes
Frequency Mode Priority Switching Frequency
Program
Fundamental
Standard Mode Selection
This parameter sets the threshold frequency that will be used to determine if
Frequency Source 1
or
2
will control the output of the ASD when
Frequency
Source 1 Priority
or
Frequency Source 2 Priority
.
See
for additional information on this setting.
Direct Access Number — F208
Parameter Type —
Numerical
Factory Default —
1.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — Maximum Freq. (
Units — Hz
Analog Input Filter
Program
Frequency
Analog Filter
Analog filtering is applied after the analog reference signal is converted to a
digital signal. The type of filtering used is
Rolling Average
over time.
Settings:
0 — None
1 — Small
2 — Medium
3 — Large
The analog input signal is sampled and converted to a digital signal. With no
filtering applied, the digital value from the conversion is scaled for use by the
microprocessor of the ASD.
If the filtering selection is
Small
, the ASD averages the last 5 sampled (digital)
values. The rolling average is updated (every 4 µS) and scaled for use by the
microprocessor.
If the filtering selection is
Medium
, the ASD averages the last 20 sampled
(digital) values. The rolling average is updated (every 4 µS) and scaled for use
by the microprocessor.
If the filtering selection is
Large
, the ASD averages the last 50 sampled
(digital) values. The rolling average is updated (every 4 µS) and scaled for use
by the microprocessor.
False responses to electrical noise are eliminated with no loss in bandwidth
because the value used by the drive is the average value of several samples.
Direct Access Number — F209
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
Yes
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......