94
WX9 ASD Installation and Operation Manual
Motor Overload Protection Level 3
Program
Motor
Motor Set 3
The
Motor Overload Protection Level 3
parameter specifies the motor
overload current level for
Motor Set 3
. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to
Amps
(V/A) or it
may be set as a percentage of the ASD rating. The name-plated FLA of the
motor may be entered directly when
Amps
is selected as the unit of
measurement (see
Current/Voltage Units Setup
to change the display
unit).
Motor Overload Protection Level
settings
(1 – 4) will be displayed in
Amps
if the
EOI
display units are set to
V/A
rather than
%
.
Direct Access Number — F177
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 100.0
Units — %
Base Frequency 4
Program
Motor
Motor Set 4
The
Base Frequency 4
setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The
Maximum Output Voltage
for
Base Frequency 4
is set at
This parameter is used only when the parameters for
Motor Set 4
are
configured and selected.
Motor Set 4
may be selected by a properly configured
input terminal.
For proper motor operation, the
Base Frequency
should be set for the name-
plated frequency of the motor.
Direct Access Number — F178
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency Voltage 4
Program
Motor
Motor Set 4
The
Base Frequency Voltage 4
is the
Motor
4
output voltage at the
Base
Frequency
). Regardless of the programmed value, the output voltage
cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the
Supply Voltage Compensation
This parameter is used only when the parameters for
Motor Set 4
are
configured and selected.
Motor Set 4
may be selected by a properly configured
input terminal.
Direct Access Number — F179
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Manual Torque Boost 4
Program
Motor
Motor Set 4
The
Manual Torque Boost 4
function
is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the
Base Frequency 4
setting
See
Manual Torque Boost 1
(
for an explanation of torque boost.
This parameter is used only when the parameters for
Motor Set
4
are
configured and selected.
Motor Set 4
may be selected by a properly configured
input terminal.
Direct Access Number — F180
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......