92
WX9 ASD Installation and Operation Manual
OUT6 Off Delay
Program
Terminal
Output Terminal Delays
This parameter delays the opening of the
OUT6
output terminals by the
programmed value (see waveforms at
).
The delay may be increased to prevent relay chatter.
Direct Access Number — F165
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 Off Delay
Program
Terminal
Output Terminal Delays
This parameter delays the opening of the
OUT7
output terminals by the
programmed value (see waveforms at
).
The delay may be increased to prevent relay chatter.
Direct Access Number — F166
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Base Frequency 2
Program
Motor
Motor Set 2
The
Base Frequency 2
setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The
Base Frequency Voltage 2
parameter
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
For proper motor operation, the
Base Frequency
should be set for the name-
plated frequency of the motor.
Direct Access Number — F170
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency Voltage 2
Program
Motor
Motor Set 2
The
Base Frequency Voltage 2
is the
Motor
2
output voltage at the
Base
Frequency 2
). Regardless of the programmed value, the output voltage
cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the
Supply Voltage Compensation
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
Direct Access Number — F171
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Manual Torque Boost 2
Program
Motor
Motor Set 2
The
Manual Torque Boost 2
function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the
Base Frequency 2
setting
See
Manual Torque Boost 1
) for an explanation of torque boost.
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
Direct Access Number — F172
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......