Meets or Exceeds 

Your Specifications

Standard Specifications

Item 

Voltage Class 

460V 

Maximum HP 

60 

75 

100 

125 

150 

200 

250 

300 

400 

500 

600 

700 

800 

Drive Rating (A) 

77 

96 

124 

156 

190 

240 

302

370 

480 

628 

753 

879 

1004 

Dimensions 

100”H x 30”W x 24”D 

100”H x 42”W x 24”D 

Consult Factory 

Power Requirements 

Output Frequency 

0 – 400 Hz 

Main Circuit 

Three Phase 460V input auto-transformer 18 pulse design with circuit breaker, IGBT output. 

Control Power 

DC bus control power 

Tolerance 

Voltage: ±10% Frequency: ±2% 

Control Specifications 

Control Method 

Sine Wave PWM System – Flux Field Current Vector Control 

V/Hz Control 

Constant Torque, Variable Torque, Open Loop Vector, Auto or Manual Torque Boost, 5 point V/Hz custom curves 

Overload Rating 

120% for 60 seconds, 100% continuous 

Frequency Setting 

Encoder Potentiometer integrated into EOI, 0-10V, ±10V, 4-20mA, Binary Input, Motorized Potentiometer Input 

Frequency Precision 

Analog Input: ±0.2% of maximum output frequency. Digital Input: ±0.01% of maximum output frequency

Frequency Resolution 

0.01 Hz – Operation Panel. 0.1 Hz – Analog Input. 10-12 bit A-D converter 

Acceleration / Deceleration 

0.1~6000 seconds 

Speed Regulation 

Up to 0.1%, 60:1 speed range 

Torque Regulation 

10%; less than 3% ripple from 50 to 100% range

Set Point Control (PID) 

Proportional Gain, Integral Gain, Feedback Settings Upper/Lower Deviation Limits, Feedback Source Delay Filter, Feedback 

Settings Differential Gain 

Analog Inputs 

Four programmable: (1) 4-20mA, (1) 0-10V, (1) -10 to +10V, (1) 1 to 10kOHM potentiometer connection 

Analog Outputs 

Two programmable to 31 functions 

Digital Inputs 

Eight programmable to 67 functions 

Output Contacts 

Three output terminals, programmable to 52 functions. Form C contacts rated 250V AC, 2 amps inductive 

Signal Isolation 

Available (3) channel signal isolation for AM/FM outputs and II terminal input, rated at 750V 

Control Board 

Communication Ports 

RS232 / 485 and TTL ports standard 

Data Transmission 

Profibus, Devicenet, Modbus RTU, , Metysys, TCP/IP Ethernet. (Some devices are external) 

Main Protective 

Functions

Current limit, overcurrent, overvoltage, undervoltage, overtorque, load side short circuit, load side ground fault, heatsink 

overheat, ASD overload, motor overload, armature short, CPU error, open output phase, communications error, loss of feedback

Soft Stall 

Automatic load reduction control during overload 

Retry 

Can automatically clear fault upon trip. Programmable to 10 tries, with up to 10 seconds between tries. 

Restart 

Restart into a rotating motor 

Interface 

LCD EOI (Liquid Crystal 

Display / Electronic 

Operator Interface) 

4 lines x 20 characters. Backlit LCD Display. Ability to display multiple parameters on one screen. Keypad may be operated from 

an external power source. Software is flash upgradeable. Includes multi-function rotary encoder. 

LED Indicators

Run (Red) / Stop (Green), Remote / Local (Green), DC bus charge indication (red) 

Keys 

Local /Remote, Monitor / Program, Run, Enter, ESC, Stop / Reset, Up, Down 

Monitoring 

Main display shows two monitored items continuously, or scrolls up to 40 items. 

Selectable Display Units 

User selectable and configurable, along with scaling factor multiplier. Voltage display selectable: Amps or %, 

Current display selectable: Amps or %. 

EOI Communication Ports 

RS232 / 485 and TTL ports standard 

Remote Mount Display 

Remote mountable up to 1000ʼ 

Construction 

Enclosure 

NEMA 1, IP20, Gasketed and Filtered 

Panel Construction 

Free standing, front maintenance type, top or bottom access for motor and power cables 

Cooling 

Forced air cooled. Top-mounted fans may be removed for movement during shipment or installation. 

Color 

ANSI-61 Gray 

Ambient Conditions 

Ambient Temperature 

0 - 40°C, 32 - 104°F 

Humidity 

Max. 95% (non-condensing) 

Altitude 

1000 m (3300 ft) above sea level or less 

Installation 

Indoor, no direct sunlight, protect for corrosive gases, explosive gases 

Standards

Electrical Performance

NEC, ANSI 

W7 Specifications

Содержание W7 Series

Страница 1: ...W7 Series ADJUSTABLE SPEED DRIVES 18 Pulse ...

Страница 2: ... latest technology and proven reliability Patented 18 Pulse Design Small Footprint Powerful User Friendly Operator Interface Variety of Communication Options 1 Small Footprint with Uniform 24 Depth 2 User Friendly Electronic Operator Interface 3 Variety of User Configurable Options 4 Gasketed and Filtered Enclosure Force Ventilated 5 Top or Bottom Cable Entry Exit 6 65 000 AIC Breaker 7 Proven Tos...

Страница 3: ...1 13 17 19 23 25 29 31 35 37 41 43 47 49 HARMONIC NUMBER 6 Pulse Typical 18 Pulse W7 e 60 Hz 113 Hz Ch1 500mV Ch2 5 00mVΩ M2 00ms Ch1 10mV Current Voltage Small Footprint The high cost of real estate and constraints of existing facilities make size an important consideration in drive selection 400 HP Drive Only 42 Wide 24 Depth on All Sizes Integrated Phase Shifting Autotransformer Saves Real Esta...

Страница 4: ...mote Mount up to 1 000 Feet Real Time Clock Option Flash Upgradeable EOI Software Display multiple parameter simultaneously Standard Keypad Design for Low Voltage and Medium Voltage Drives Variety of Communication Options In todayʼs fast paced manufacturing world coordinated systems require communications from drive to drive and drive to system Built in ports and a variety of option cards provide ...

Страница 5: ...t 750V Control Board Communication Ports RS232 485 and TTL ports standard Data Transmission Profibus Devicenet Modbus RTU Modbus Metysys TCP IP Ethernet Some devices are external Main Protective Functions Current limit overcurrent overvoltage undervoltage overtorque load side short circuit load side ground fault heatsink overheat ASD overload motor overload armature short CPU error open output phas...

Страница 6: ...ow More Be sure to visit our web site located at www tic toshiba com for the latest information on Toshiba s products Customer Support Services Toshiba offers 24 hour service nationwide For assistance of any type call 1 800 231 1412 Medium Voltage Motor G7 Drive ADJUSTABLE SPEED DRIVES MOTORS CONTROLS UPS INSTRUMENTATION PLC INDUSTRIAL DIVISION 13131 West Little York Road Houston Texas 77041 Tel 7...

Отзывы: