Standard default setting
V[R
: Standard setting mode selection
Title
Function
Adjustment range
Default setting
V[R
Standard setting
mode selection
0 : -
1 : Default setting 50Hz
2 : Default setting 60Hz
3 : Default setting
4 : Trip clear
5 : Cumulative operation time clear
0
★
This function will be displayed as 0 during reading on the right. This previous setting is
displayed on the left.
Ex. 3
0
★
V[R
cannot be set during the inverter operating. Always stop the inverter first and then program.
[Setting values]
50Hz standard setting
(
V[R
=
)
To set the following parameters for a base frequency of 50Hz, set the
V[R
parameter to 1.
(This setting does not affect the settings of any other parameters.)
•
Maximum frequency
HJ
: 50Hz
•
Base frequency 1
XN
: 50Hz
•
Base frequency 2
H
: 50Hz
•
Upper limit frequency
WN
: 50Hz
•
VI/S3 point 2 frequency
H
: 50Hz
•
Motor rated speed
H
: 1410min
-1
60Hz standard setting
(
V[R
=
)
To set the following parameters for a base frequency of 60Hz, set the
V[R
parameter to 2.
(This setting does not affect the settings of any other parameters.)
•
Maximum frequency
HJ
: 60Hz
•
Base frequency 1
XN
: 60Hz
•
Base frequency 2
H
: 60Hz
•
Upper limit frequency
WN
: 60Hz
•
VI/S3 point 2 frequency
H
: 60Hz
•
Motor rated speed
H
: 1710min
-1
Default setting
(
V[R
=
)
Setting
V[R
to
will return all parameters to the standard values that were programmed at the
factory.
☆
When 3 is programmed, <
KPKV
will be displayed for a short time after setting and will then
be erased and displayed the original indication “
PQ
” (Setup parameter). (Only for VFNC1 (S)-
□□□□
P
□
-W type) This setting clears all trip history data but it does not clear cumulative
operation time data. This setting does not affect the settings of the following parameters.
•
FM/OUT terminal functions selection
HOUN
•
Meter adjustment
HO
•
Analog input/logic input function selection
H
•
Sink/source selection
H
•
Free notes
H
See 4.1.1 for setting of setup parameters.
Trip clear
(
V[R
=
)
Setting
V[R
to
initializes the past four sets of recorded error history data.
* (The parameter does not change.)
Cumulative operation time clear
(
V[R
=
)
Setting
V[R
to
allows the initial resetting of the cumulative operation time monitor (0 [zero]
time).
* (The parameter does not change.)
•
Function
Allows setting of all parameters to the standard default setting, etc. at one time. (Except
the setting of
HO
)