E6582062
6. [Advanced] How to use parameters
6-146
4
4
6
9
6. 30. 18 Rush current suspension relay control
<F635: Rush current suppression relay delay time>
■
Function
This function is used for DC input or when multiple inverters are connected with DC section and
when the rush current suspension resistor relay needs to be controlled.
■
Parameter setting
■
Guideline for the setting
When the voltage of DC section in the inverter has reached the specified voltage, after a lapse of
setting time by <F635: Rush current suppression relay delay time> +500ms (basic wait time), the
rush current suspension relay is turned on.
Title
Parameter name
Adjustment range
Unit
Default setting
F635
Rush current
suppression relay delay
time
0.0 - 2.5
s
0.0
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
0.0Hz
STOP
14:03
F635 : Rush current relay time
Min: 0.0
Max: 2.5
X1000
X100
X10
X1
S
0.0
Voltage in the DC section
Rush current suppression relay
ON
<F635>
+500ms
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...