6. [Advanced] How to use parameters
3
4
6
9
<F354: Commercial power/Inverter switching>
<F355: Commercial power switching frequency>
<F356: Inverter switching wait time>
<F357: Commercial power switching wait time>
<F358: Commercial power switching frequency continu-
ous time>
■
Function
This function allows output of switching signals to an external sequence (such as MC) so that when
tripping occurs, operation will be switched to commercial power run without stopping the motor.
For details, refer to Commercial power/Inverter switching (E6582108).
■
Parameter setting
Trips that are automatically switched are those not displayed as "OCL", "E", "EF1", and "EF2".
<F341: Brake function> will not be enabled.
6. 20 Switching to commercial power run
Title
Parameter name
Adjustment range
Unit
Default setting
F354
Commercial power/
Inverter switching
0: Disabled
1: Switch at trip
2: Switch at F355
3: Switch at trip and at F355
0
F355
Commercial power
switching frequency
0 - UL
Hz
50.0/60.0
*1
*1 Depending on the setup menu. Refer to [5. 3. 10], [11. 10].
F356
Inverter switching wait
time
0.10 - 10.00
s
*2
*2 Depending on capacity. For details, refer to [11. 5].
F357
Commercial power
switching wait time
0.10 - 10.00
s
0.62
F358
Commercial power
switching frequency
continuous time
0.10 - 10.00
s
2.00
0: Disabled
1: Switch at trip
2: Switch at F355
0.0Hz
STOP
13:22
F354 : CP/ inverter seitch
3: Switch at trip and at F355
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...