Terminal Connections and Functions (cont'd)
5 - 6
Terminal
Terminal functions
Terminal
name
location
ST
Input terminal for run interlock. When ST is shorted to CC, the inverter
is ready to run. With ST-CC open the unit will not run and if opened
while running a coasting stop begins.
F
Input terminal for forward run. When F is shorted to CC, a forward
run starts. With F-CC open, the unit decelerates to a complete stop.
R
Input terminal for reverse run. When R is shorted to CC, a reverse run
starts. With R-CC open, the unit decelerates to a complete stop.
If terminals F-CC and R-CC are shorted simultaneously, a reverse
run occurs.
CC
This is the common return for ST terminal.
(one of three)
Do not connect to GND(E).
SS1
Input terminal for multi-speed run frequencies. Depends on setting of
function [1.tb], JOG/SS2 and AD2/SS3 terminals. (See Page 10-1)
JOG(SS2)
Input terminal for jogging run or multi-speed run frequencies. Depends
on setting of function [1.tb], SS1, AD2(SS3) terminals. (See Page 10-1)
AD2(SS3)
Input terminal for multispeed run frequencies. Depends on setting of
function [1.tb], SS1, JOG/SS2 terminals. (See Page 10-1)
RST
With RST-CC shorted, the inverter's protective function resets.
CC
This is the common return for ST, F, R, SS1, JOG(SS2), AD2(SS3),
(one of three)
and RST terminals.
Do not connect to GND(E).
GND(E)
The inverter earth ground terminal.
(three provided)
Do not connect to common return terminal (CC).
R41/46 **
Jumper to RJ when using 415V-50Hz/460V-60Hz incoming power.
Do not jumper to R40/44 or R38.
R40/44 ***
Jumper to RJ when using 400V-50Hz/440V-60Hz incoming power.
Do not jumper to R41/46 or R38.
R38
Jumper to RJ when using 380V-50Hz incoming power.
Do not jumper to R41/46 or R40/44.
RJ
Common for input power selection. Jumper to either R41/46, R40/44,
or R38.
Do not jumper to more than one terminal at a time.
Frame
screw or
lug
Control
PWB
terminal
block
Terminal
block *
* For models P2-440KB to P2-470KB, the input voltage selection is made directly at the control
power transformer T1.
** For model P2-430KB, jumper RJ to R46 if the input voltage selection is 460V - 60Hz.
*** For model P2-430KB, jumper RJ to R40 if the input voltage selection is 415V - 50Hz.