FILE NO. SVM-13092
1
Electrolytic capacitor
1. Turn OFF the power supply breaker.
(For raising pressure, smoothing)
2. Discharge all three capacitors completely.
3. Check that safety valve at the bottom of capacitor is not broken.
4. Check that vessel is not swollen or exploded.
5. Check that electrolytic liquid does not blow off.
6. Check that the normal charging characteristics are show in
continuity test by the tester.
C07, C08, C09
→
500
µ
F/400V or 760
µ
F/400V
2
Converter module
1. Turn OFF the power supply breaker.
2. Discharge all three capacitors completely.
3 Check that the normal rectification characteristics are shown in continuity
test by the tester.
11-8-5. Checking Method for Each Part
Case that product is good
Pointer swings once, and
returns slowly. When
performing test once again
under another polarity, the
pointer should return.
No.
Part name
Checking procedure
5 Outdoor temperature sensor
Diode check
e
d
d
e
\
1
~
\
2
~
\
1
~
\
2
~
(TO), discharge temperature
1
2
sensor (TD), suction temperature
Tester rod
Resistance value
e
in good product
xchanger temper
50k
Ω
or more
(0
Ω
in trouble)
~
+
–
~
1 2 3
(DB
0
1)
4
ature sensor
(TE)
Disconnect the connector, and measure resistance value with the tester.
(Normal temperature)
TGa : Heat pump model only.
TO, TE : Refer to the TA, TC characteristic table in Indoor
(Refer to Table 10-8-3, No.1).
Temperature
10°C
20°C
30°C
40°C
50°C
Sensor
TA, TC (k
Ω
) 105 64 41 27 18
– 81 –